![background image](http://html.mh-extra.com/html/siemens/simpro-100/simpro-100_instruction-manual_383121215.webp)
SIMPRO-100
SIMPRO-100 Relay Settings Sheets
F
PRIM-2400C
213
F SIMPRO-100 Relay Settings Sheets
F.1
Relay Settings
(Factory Defaults, Model 100101X)
F.1.1
General Data
Relay Identifier
Range: 20 Characters
RID =
[SIMPRO-100]
Terminal Identifier
Range: 20 Characters
TID =
[Motor Relay]
Phase (IA, IB, IC) CT Ratio
Range: 1 – 6000
CTR =
[100]
Phase CT Secondary Rating
Range: 1 A, 5 A
ITAP =
[5]
Neutral (IN) CT Ratio
Range: 1 – 6000
CTRN =
[100]
Neutral CT Secondary Rating
Range: 1 A, 5 A
INTAP =
[5]
Phase Rotation
Range: ABC, ACB
PHROT =
[ABC]
Nominal Frequency
Range: 50, 60 Hz
FNOM =
[60]
Date Format
Range: MDY, YMD
DATE_F =
[MDY]
Demand Meter Time Constant
Range: 5, 10, 15, 30, 60 min
DTMC =
[15]
Phase (VA, VB, VC) VT Ratio
(Hidden if voltages not included.)
Range: 1 – 6000
PTR =
[100]
Phase VT Connection
(Hidden if voltages not included.)
Range: D, Y
DELTA_Y =
[Y]
Single Voltage Input
(Hidden if voltages not included.)
Range: Y, N
SINGLEV =
[N]
Summary of Contents for SIMPRO-100
Page 1: ...SIMPRO 100 Motor Protection Relay Instruction Manual Document No PRIM 2400C ...
Page 12: ...Contents SIMPRO 100 x PRIM 2400C ...
Page 16: ...Contents SIMPRO 100 xiv PRIM 2400C ...
Page 42: ...3 SIMPRO PC Software SIMPRO 100 40 PRIM 2400C ...
Page 100: ...6 ASCII Serial Port Operation SIMPRO 100 98 PRIM 2400C ...
Page 127: ...SIMPRO 100 Event Analysis 9 PRIM 2400C 125 Figure 9 2 Example SER Report ...
Page 136: ...10 Maintenance Troubleshooting SIMPRO 100 134 PRIM 2400C ...
Page 138: ...A Firmware Versions SIMPRO 100 136 PRIM 2400C ...
Page 206: ...D SIMPRO PC Compatibility Features SIMPRO 100 204 PRIM 2400C ...
Page 214: ...E Motor Thermal Element SIMPRO 100 212 PRIM 2400C ...
Page 230: ...F SIMPRO 100 Relay Settings Sheets SIMPRO 100 228 PRIM 2400C ...
Page 239: ......