![background image](http://html.mh-extra.com/html/siemens/simpro-100/simpro-100_instruction-manual_383121218.webp)
F
SIMPRO-100 Relay Settings Sheets
SIMPRO-100
216
PRIM-2400C
The balance of Thermal Element Settings are used
regardless of setting method.
Thermal Capacity Alarm Pickup
Range: 50% – 100%
TCAPU =
[90]
Thermal Capacity Used to Start
Range: 20% – 100%
TCSTART =
[85]
Use Learned Starting Thermal Capacity
Range: Y, N
TCLRNEN =
[Y]
Motor Stopped Cooling Time
Range: 180 – 72000 s
COOLTIME =
[259]
Use Learned Cooling Time
Range: Y, N
COOLEN =
[Y]
F.1.3
Overcurrent (O/C)
Elements
(Time-delay settings are
hidden when their associated pickup settings
= OFF)
Level 1 Phase O/C Pickup
Range: OFF, 0.25 – 100.00 A; ITAP = 5 A
Range: OFF, 0.05 – 20.00 A; ITAP = 1 A
50P1P =
[OFF]
Level 1 Phase O/C Time Delay
Range: 0.00 – 400.00 s
50P1D =
[Hidden]
Level 2 Phase O/C Pickup
Range: OFF, 0.25 – 100.00 A; ITAP = 5 A
Range: OFF, 0.05 – 20.00 A; ITAP = 1 A
50P2P =
[OFF]
Level 2 Phase O/C Time Delay
Range: 0.00 – 400.00 s
50P2D =
[Hidden]
Level 1 Residual O/C Pickup
Range: OFF, 0.25 – 100.00 A; ITAP = 5 A
Range: OFF, 0.05 – 20.00 A; ITAP = 1 A
50G1P =
[2.50]
Level 1 Residual O/C Time Delay
Range: 0.00 – 400.00 s
50G1D =
[0.10]
Level 2 Residual O/C Pickup
Range: OFF, 0.25 – 100.00 A; ITAP = 5 A
Range: OFF, 0.05 – 20.00 A; ITAP = 1 A
50G2P =
[OFF]
Level 2 Residual O/C Time Delay
Range: 0.00 – 400.00 s
50G2D =
[Hidden]
Level 1 Neutral O/C Pickup
Range: OFF, 0.025 – 10.000 A; INTAP = 5A
Range: OFF, 0.005 – 2.000 A; INTAP = 1 A
50N1P =
[2.500]
Level 1 Neutral O/C Time Delay
Range: 0.00 – 400.00 s
50N1D =
[0.10]
Level 2 Neutral O/C Pickup
Range: OFF, 0.025 – 10.000 A; INTAP = 5 A
Range: OFF, 0.005 – 2.000 A; INTAP = 1 A
50N2P =
[OFF]
Level 2 Neutral O/C Time Delay
Range: 0.00 – 400.00 s
50N2D =
[Hidden]
Summary of Contents for SIMPRO-100
Page 1: ...SIMPRO 100 Motor Protection Relay Instruction Manual Document No PRIM 2400C ...
Page 12: ...Contents SIMPRO 100 x PRIM 2400C ...
Page 16: ...Contents SIMPRO 100 xiv PRIM 2400C ...
Page 42: ...3 SIMPRO PC Software SIMPRO 100 40 PRIM 2400C ...
Page 100: ...6 ASCII Serial Port Operation SIMPRO 100 98 PRIM 2400C ...
Page 127: ...SIMPRO 100 Event Analysis 9 PRIM 2400C 125 Figure 9 2 Example SER Report ...
Page 136: ...10 Maintenance Troubleshooting SIMPRO 100 134 PRIM 2400C ...
Page 138: ...A Firmware Versions SIMPRO 100 136 PRIM 2400C ...
Page 206: ...D SIMPRO PC Compatibility Features SIMPRO 100 204 PRIM 2400C ...
Page 214: ...E Motor Thermal Element SIMPRO 100 212 PRIM 2400C ...
Page 230: ...F SIMPRO 100 Relay Settings Sheets SIMPRO 100 228 PRIM 2400C ...
Page 239: ......