F
SIMPRO-100 Relay Settings Sheets
SIMPRO-100
222
PRIM-2400C
F.2.3
Undervoltage (U/V)
Elements
(Hidden if no voltage option
or if DELTA_Y = D)
Level 1 Phase U/V Pickup
Range: OFF, 1 – 300 V
27P1P =
[OFF]
Level 2 Phase U/V Pickup
Range: OFF, 1 – 300 V
27P2P =
[OFF]
F.2.4
Overvoltage (O/V)
Elements
(Hidden if no voltage option
or if DELTA_Y = D)
Level 1 Phase O/V Pickup
Range: OFF, 1 – 300 V
59P1P =
[73]
Level 2 Phase O/V Pickup
Range: OFF, 1 – 300 V
59P2P =
[OFF]
Residual O/V Pickup
(Hidden if SINGLEV = Y)
Range: OFF, 1 – 300 V
59GP =
[OFF]
F.2.5
Reactive Power (VAR)
Element Settings
(Hidden if no
voltage option)
Negative VAR Alarm Pickup
Range: OFF, 30 – 2000 VAR; ITAP = 5 A
OFF, 6 – 400 VAR; ITAP = 1 A
NVARAP =
[OFF]
Positive VAR Alarm Pickup
(Hidden if NVARAP = OFF)
Range: 30 – 2000 VAR; ITAP = 5 A
6 – 400 VAR; ITAP = 1 A
PVARAP =
[Hidden]
VAR Alarm Time Delay
(Hidden if NVARAP = OFF)
Range: 0.00 – 400.00 s
VARAD =
[Hidden]
Negative VAR Trip Pickup
Range: OFF, 30 – 2000 VAR; ITAP = 5 A
OFF, 6 – 400 VAR; ITAP = 1 A
NVARTP =
[OFF]
Positive VAR Trip Pickup
(Hidden if NVARTP = OFF)
Range: 30 – 2000 VAR; ITAP = 5 A
6 – 400 VAR; ITAP = 1 A
PVARTP =
[Hidden]
VAR Trip Time Delay
(Hidden if NVARTP = OFF)
Range: 0.00 – 400.00 s
VARTD =
[Hidden]
VAR Element Arming Delay
(Hidden if both NVARAP and NVARTP = OFF)
Range: 0.00 – 15000 s
VARDLY =
[Hidden]
F.2.6
Underpower Element
Settings
(Hidden if no voltage option)
Phase Underpower Alarm Pickup
Range: OFF, 30 – 2000 W; ITAP = 5 A
OFF, 6 – 400 W; ITAP = 1 A
37PAP =
[OFF]
Phase Underpower Alarm Time Delay
(Hidden if 37PAP = OFF)
Range: 0.00 – 400.00 s
37PAD =
Phase Underpower Trip Pickup
Range: OFF, 30 – 2000 W; ITAP = 5 A
OFF, 6 – 400 W; ITAP = 1 A
37PTP =
[OFF]
Summary of Contents for SIMPRO-100
Page 1: ...SIMPRO 100 Motor Protection Relay Instruction Manual Document No PRIM 2400C ...
Page 12: ...Contents SIMPRO 100 x PRIM 2400C ...
Page 16: ...Contents SIMPRO 100 xiv PRIM 2400C ...
Page 42: ...3 SIMPRO PC Software SIMPRO 100 40 PRIM 2400C ...
Page 100: ...6 ASCII Serial Port Operation SIMPRO 100 98 PRIM 2400C ...
Page 127: ...SIMPRO 100 Event Analysis 9 PRIM 2400C 125 Figure 9 2 Example SER Report ...
Page 136: ...10 Maintenance Troubleshooting SIMPRO 100 134 PRIM 2400C ...
Page 138: ...A Firmware Versions SIMPRO 100 136 PRIM 2400C ...
Page 206: ...D SIMPRO PC Compatibility Features SIMPRO 100 204 PRIM 2400C ...
Page 214: ...E Motor Thermal Element SIMPRO 100 212 PRIM 2400C ...
Page 230: ...F SIMPRO 100 Relay Settings Sheets SIMPRO 100 228 PRIM 2400C ...
Page 239: ......