PRIM-2400C
225
F.3.5
Antibackspin Setting
Antibackspin Starting Delay
Range: 0 – 60 min
ABSDLY =
[0]
F.3.6
Factory Logic Settings
Use Factory Logic Settings
Range: Y, N
FACTLOG =
[Y]
F.4
Serial Port Settings
(Serial Port Command SET P F or SET P R)
F.4.1
SET P Serial Port Settings
Protocol
(Hidden, Equal ASCII for Front Port)
Range: ASCII, MOD
PROTO =
[ASCII]
F.4.1.1
Protocol = ASCII
(Hidden when Protocol = MOD)
Baud Rate
Range: 300 – 19200
SPEED =
[2400]
Data Bits
Range: 7, 8
BITS =
[8]
Parity
Range: O, E, N
PARITY =
[N]
Stop Bits
Range: 1, 2
STOP =
[1]
Timeout
Range: 0 – 30 min
T_OUT =
[15]
Send Auto Messages to Port
Range: Y, N
AUTO =
[N]
Enable Hardware Handshaking
Range: Y, N
RTSCTS =
[N]
Fast Operate Enable
Range: Y, N
FASTOP =
[N]
F.4.1.2
Protocol = MOD
(Hidden when Protocol = ASCII)
Baud Rate
Range: 300 – 19200
SPEED =
[2400]
Parity
Range: O, E, N
PARITY =
[N]
Modbus
®
Slave ID
Range: 1 – 247
SLAVEID =
Summary of Contents for SIMPRO-100
Page 1: ...SIMPRO 100 Motor Protection Relay Instruction Manual Document No PRIM 2400C ...
Page 12: ...Contents SIMPRO 100 x PRIM 2400C ...
Page 16: ...Contents SIMPRO 100 xiv PRIM 2400C ...
Page 42: ...3 SIMPRO PC Software SIMPRO 100 40 PRIM 2400C ...
Page 100: ...6 ASCII Serial Port Operation SIMPRO 100 98 PRIM 2400C ...
Page 127: ...SIMPRO 100 Event Analysis 9 PRIM 2400C 125 Figure 9 2 Example SER Report ...
Page 136: ...10 Maintenance Troubleshooting SIMPRO 100 134 PRIM 2400C ...
Page 138: ...A Firmware Versions SIMPRO 100 136 PRIM 2400C ...
Page 206: ...D SIMPRO PC Compatibility Features SIMPRO 100 204 PRIM 2400C ...
Page 214: ...E Motor Thermal Element SIMPRO 100 212 PRIM 2400C ...
Page 230: ...F SIMPRO 100 Relay Settings Sheets SIMPRO 100 228 PRIM 2400C ...
Page 239: ......