![background image](http://html.mh-extra.com/html/siemens/simpro-100/simpro-100_instruction-manual_383121025.webp)
SIMPRO-100
Introduction & Specifications
1
PRIM-2400C
23
1.7.2
Communication Cables
Remember to order required serial
communication cables with the relay.
•
Use Siemens Cable SIM-232 or a null-modem
cable to connect the relay front-panel serial
port to a PC 9-pin serial port for setting upload
and download and for other activities during
relay installation and operation. This cable is
not included with the relay. You can purchase
this cable separately from Siemens or build
your own using the cable pinout shown in
Section 6.3, page 86.
•
Use fiber-optic cable SIM-RTD-XXX (xxx =
number meters) to connect the relay rear-
panel fiber-optic receiver port to a
SIMPRO-100-RTD External RTD Module.
You can also purchase this cable directly from
Siemens.
1.7.3
Place a Request for
Quotation or Order
You may order a SIMPRO-100 Relay from your
local Siemens relay supplier.
1.8
SIMPRO-100 Relay
Serial Number Label
Figure 1.2
SIMPRO-100 Relay Serial Number Label
Figure 1.2 shows the serial number label for the
SIMPRO-100 Relay. The label is affixed to the top
of the relay chassis. From the top of the label, the
information includes:
•
Relay part number
•
Relay serial number
•
Power supply ratings
•
AC current input ratings
•
AC voltage input ratings, or None if voltage
option was not ordered
•
Number of internal RTD inputs, either 11 or
None
1.9
Detailed
Specifications
1.9.1
Standard Relay Features &
Functions
Phase Current Inputs
Nominal Current, I
NOM
: 1 A or 5 A
Range:
0.05 – 20.00 • I
NOM
Burden:
0.14 VA @ 5 A, 5 A tap
0.06 VA @ 1 A, 1 A tap
Continuous:
3 • I
NOM
200 Second Thermal:
10 • I
NOM
10 Second Thermal:
20 • I
NOM
1 Second Thermal:
50 • I
NOM
Measuring Error:
< ± 1%, Full Scale
Neutral/Ground Current Input
Nominal
Current, IN
NOM
:
1 A or 5 A
Range:
0.005 – 2.000 • IN
NOM
Burden:
0.28 VA @ 5 A, 5 A tap
0.19 VA @ 1 A, 1 A tap
Continuous:
0.3 • IN
NOM
1 Second Thermal:
5.0 • IN
NOM
Measuring Error:
< ± 1%, Full Scale
Summary of Contents for SIMPRO-100
Page 1: ...SIMPRO 100 Motor Protection Relay Instruction Manual Document No PRIM 2400C ...
Page 12: ...Contents SIMPRO 100 x PRIM 2400C ...
Page 16: ...Contents SIMPRO 100 xiv PRIM 2400C ...
Page 42: ...3 SIMPRO PC Software SIMPRO 100 40 PRIM 2400C ...
Page 100: ...6 ASCII Serial Port Operation SIMPRO 100 98 PRIM 2400C ...
Page 127: ...SIMPRO 100 Event Analysis 9 PRIM 2400C 125 Figure 9 2 Example SER Report ...
Page 136: ...10 Maintenance Troubleshooting SIMPRO 100 134 PRIM 2400C ...
Page 138: ...A Firmware Versions SIMPRO 100 136 PRIM 2400C ...
Page 206: ...D SIMPRO PC Compatibility Features SIMPRO 100 204 PRIM 2400C ...
Page 214: ...E Motor Thermal Element SIMPRO 100 212 PRIM 2400C ...
Page 230: ...F SIMPRO 100 Relay Settings Sheets SIMPRO 100 228 PRIM 2400C ...
Page 239: ......