Settings Calculation
SIMPRO-100
50
PRIM-2400C
4.4.1.3
Thermal Element USER Setting Method
Table 4.10
Thermal Element Configuration Settings, Setting Method = USER
When the thermal element setting method is set
to USER, the relay allows you to construct a
custom motor protection curve using as few as 5
or as many as 25 thermal limit points. The relay
requires:
•
The Full Load Amps and Service Factor
ratings for the motor
•
Time to Trip settings at 2.00 and 2.50 times
Full Load Amps for overload protection
•
Time to Trip settings at 5.50, 6.00, and 6.50
times Full Load Amps for locked rotor
protection
Setting Prompt
Setting Range
Setting Name =
Example Setting
Setting Method
Rating, Generic, User
SETMETH = USER
Full Load Amps
2.50 – 8.00 A ITAP = 5 A
0.50 – 1.60 A ITAP = 1A
FLA = 3.66
FLA = 0.732
Service Factor
1.00 – 1.50
SF = 1.25
Time to Trip at 1.05 • FLA
1.0 – 6000.0 s, NP
TTT105 = NP
Time to Trip at 1.10 • FLA
1.0 – 6000.0 s, NP
TTT110 = NP
Time to Trip at 1.20 • FLA
1.0 – 6000.0 s, NP
TTT120 = NP
Time to Trip at 1.30 • FLA
1.0 – 6000.0 s, NP
TTT130 = NP
Time to Trip at 1.40 • FLA
1.0 – 6000.0 s, NP
TTT140 = NP
Time to Trip at 1.50 • FLA
1.0 – 6000.0 s, NP
TTT150 = NP
Time to Trip at 1.75 • FLA
1.0 – 6000.0 s, NP
TTT175 = NP
Time to Trip at 2.00 • FLA
1.0 – 6000.0 s
TTT200 = NP
Time to Trip at 2.25 • FLA
1.0 – 6000.0 s, NP
TTT225 = NP
Time to Trip at 2.50 • FLA
1.0 – 6000.0 s
TTT250 = NP
Time to Trip at 2.75 • FLA
1.0 – 6000.0 s, NP
TTT275 = NP
Time to Trip at 3.00 • FLA
1.0 – 6000.0 s, NP
TTT300 = NP
Time to Trip at 3.50 • FLA
1.0 – 6000.0 s, NP
TTT350 = NP
Time to Trip at 4.00 • FLA
1.0 – 6000.0 s, NP
TTT400 = NP
Time to Trip at 4.50 • FLA
1.0 – 6000.0 s, NP
TTT450 = NP
Time to Trip at 5.00 • FLA
1.0 – 600.0 s, NP
TTT500 = NP
Time to Trip at 5.50 • FLA
1.0 – 600.0 s
TTT550 = NP
Time to Trip at 6.00 • FLA
1.0 – 600.0 s
TTT600 = NP
Time to Trip at 6.50 • FLA
1.0 – 600.0 s
TTT650 = NP
Time to Trip at 7.00 • FLA
1.0 – 450.0 s, NP
TTT700 = NP
Time to Trip at 7.50 • FLA
1.0 – 400.0 s, NP
TTT750 = NP
Time to Trip at 8.00 • FLA
1.0 – 400.0 s, NP
TTT800 = NP
Time to Trip at 8.50 • FLA
1.0 – 350.0 s, NP
TTT850 = NP
Time to Trip at 9.00 • FLA
1.0 – 300.0 s, NP
TTT900 = NP
Time to Trip at 10.00 • FLA
1.0 – 225.0 s, NP
TTT1000 = NP
Summary of Contents for SIMPRO-100
Page 1: ...SIMPRO 100 Motor Protection Relay Instruction Manual Document No PRIM 2400C ...
Page 12: ...Contents SIMPRO 100 x PRIM 2400C ...
Page 16: ...Contents SIMPRO 100 xiv PRIM 2400C ...
Page 42: ...3 SIMPRO PC Software SIMPRO 100 40 PRIM 2400C ...
Page 100: ...6 ASCII Serial Port Operation SIMPRO 100 98 PRIM 2400C ...
Page 127: ...SIMPRO 100 Event Analysis 9 PRIM 2400C 125 Figure 9 2 Example SER Report ...
Page 136: ...10 Maintenance Troubleshooting SIMPRO 100 134 PRIM 2400C ...
Page 138: ...A Firmware Versions SIMPRO 100 136 PRIM 2400C ...
Page 206: ...D SIMPRO PC Compatibility Features SIMPRO 100 204 PRIM 2400C ...
Page 214: ...E Motor Thermal Element SIMPRO 100 212 PRIM 2400C ...
Page 230: ...F SIMPRO 100 Relay Settings Sheets SIMPRO 100 228 PRIM 2400C ...
Page 239: ......