SIMPRO-100
Settings Calculation
4
PRIM-2400C
59
The relay automatically hides the Temperature
Preference setting and all other settings
associated with the RTD inputs if you set
RTDOPT equal to NONE.
4.5.2
RTD Location Settings
Table 4.24
RTD Location Settings
The relay allows you to define the location of
each monitored RTD independently using the
RTD Location settings.
Define the RTD Location settings using the
following suggestions:
•
If an RTD is not connected to an input or has
failed in place and will not be replaced, set
RTD Location for that input equal to NONE.
•
For RTDs embedded in motor stator
windings, set RTD Location equal to WDG.
•
For inputs connected to RTDs measuring
bearing race temperature, set RTD Location
equal to BRG.
•
For the input connected to an RTD measuring
ambient motor cooling air temperature, set
RTD Location equal to AMB. Only one
ambient temperature RTD is allowed.
•
For inputs connected to monitor temperatures
of other apparatus, set RTD Location equal to
OTH.
4.5.3
RTD Type Settings
Table 4.25
RTD Type Settings
Setting
Prompt
Setting Range
Setting Name =
Factory Default
RTD Location
WDG, BRG, AMB,
OTH, NONE
RTD1LOC = BRG
RTD Location
WDG, BRG, AMB,
OTH, NONE
RTD2LOC = BRG
RTD Location
WDG, BRG, AMB,
OTH, NONE
RTD3LOC = BRG
RTD Location
WDG, BRG, AMB,
OTH, NONE
RTD4LOC = BRG
RTD Location
WDG, BRG, AMB,
OTH, NONE
RTD5LOC = WDG
RTD Location
WDG, BRG, AMB,
OTH, NONE
RTD6LOC = WDG
RTD Location
WDG, BRG, AMB,
OTH, NONE
RTD7LOC = WDG
RTD Location
WDG, BRG, AMB,
OTH, NONE
RTD8LOC = WDG
RTD Location
WDG, BRG, AMB,
OTH, NONE
RTD9LOC = WDG
RTD Location
WDG, BRG, AMB,
OTH, NONE
RTD10LOC = WDG
RTD Location
WDG, BRG, AMB,
OTH, NONE
RTD11LOC = AMB
RTD Location
a
WDG, BRG, AMB,
OTH, NONE
RTD12LOC = OTH
a
The twelfth RTD input is only available when you use the
SIMPRO-100-RTD External RTD Module.
Setting
Prompt
Setting Range
Setting Name =
Factory Default
RTD Type
PT100, NI100,
NI120, CU10
RTD1TY = PT100
RTD Type
PT100, NI100,
NI120, CU10
RTD2TY = PT100
RTD Type
PT100, NI100,
NI120, CU10
RTD3TY = PT100
RTD Type
PT100, NI100,
NI120, CU10
RTD4TY = PT100
RTD Type
PT100, NI100,
NI120, CU10
RTD5TY = PT100
RTD Type
PT100, NI100,
NI120, CU10
RTD6TY = PT100
RTD Type
PT100, NI100,
NI120, CU10
RTD7TY = PT100
RTD Type
PT100, NI100,
NI120, CU10
RTD8TY = PT100
RTD Type
PT100, NI100,
NI120, CU10
RTD9TY = PT100
RTD Type
PT100, NI100,
NI120, CU10
RTD10TY = PT100
RTD Type
PT100, NI100,
NI120, CU10
RTD11TY = PT100
RTD Type
a
PT100, NI100,
NI120, CU10
RTD12TY = PT100
a
The twelfth RTD input is only available when you use the
SIMPRO-100-RTD External RTD Module.
Summary of Contents for SIMPRO-100
Page 1: ...SIMPRO 100 Motor Protection Relay Instruction Manual Document No PRIM 2400C ...
Page 12: ...Contents SIMPRO 100 x PRIM 2400C ...
Page 16: ...Contents SIMPRO 100 xiv PRIM 2400C ...
Page 42: ...3 SIMPRO PC Software SIMPRO 100 40 PRIM 2400C ...
Page 100: ...6 ASCII Serial Port Operation SIMPRO 100 98 PRIM 2400C ...
Page 127: ...SIMPRO 100 Event Analysis 9 PRIM 2400C 125 Figure 9 2 Example SER Report ...
Page 136: ...10 Maintenance Troubleshooting SIMPRO 100 134 PRIM 2400C ...
Page 138: ...A Firmware Versions SIMPRO 100 136 PRIM 2400C ...
Page 206: ...D SIMPRO PC Compatibility Features SIMPRO 100 204 PRIM 2400C ...
Page 214: ...E Motor Thermal Element SIMPRO 100 212 PRIM 2400C ...
Page 230: ...F SIMPRO 100 Relay Settings Sheets SIMPRO 100 228 PRIM 2400C ...
Page 239: ......