4
Settings Calculation
SIMPRO-100
60
PRIM-2400C
The relay allows you to define the type of each
monitored RTD independently using the RTD
Type settings.
If an RTD Location setting is equal to NONE, the
relay does not request that an RTD Type setting
be entered for that input.
The four available RTD types are:
•
100-ohm platinum (PT100)
•
100-ohm nickel (NI100)
•
120-ohm nickel (NI120)
•
10-ohm copper (CU10)
4.5.4
RTD Alarm & Trip
Temperatures
Table 4.26
RTD Alarm and Trip Temperature Settings
Setting Prompt
Setting Range
Setting Name =
Factory Default
RTD Trip Temperature
OFF, 32° – 482°F TRTMP1 = OFF
RTD Alarm Temperature OFF, 32° – 482°F ALTMP2 = OFF
RTD Trip Temperature
OFF, 32° – 482°F TRTMP2 = OFF
RTD Alarm Temperature OFF, 32° – 482°F ALTMP2 = OFF
RTD Trip Temperature
OFF, 32° – 482°F TRTMP3 = OFF
RTD Alarm Temperature OFF, 32° – 482°F ALTMP3 = OFF
RTD Trip Temperature
OFF, 32° – 482°F TRTMP4 = OFF
RTD Alarm Temperature OFF, 32° – 482°F ALTMP4 = OFF
RTD Trip Temperature
OFF, 32° – 482°F TRTMP5 = OFF
RTD Alarm Temperature OFF, 32° – 482°F ALTMP5 = OFF
RTD Trip Temperature
OFF, 32° – 482°F TRTMP6 = OFF
RTD Alarm Temperature OFF, 32° – 482°F ALTMP6 = OFF
RTD Trip Temperature
OFF, 32° – 482°F TRTMP7 = OFF
RTD Alarm Temperature OFF, 32° – 482°F ALTMP7 = OFF
RTD Trip Temperature
OFF, 32° – 482°F TRTMP8 = OFF
RTD Alarm Temperature OFF, 32° – 482°F ALTMP8 = OFF
RTD Trip Temperature
OFF, 32° – 482°F TRTMP9 = OFF
RTD Alarm Temperature OFF, 32° – 482°F ALTMP9 = OFF
RTD Trip Temperature
OFF, 32° – 482°F TRTMP10 = OFF
RTD Alarm Temperature OFF, 32° – 482°F ALTMP10 = OFF
RTD Trip Temperature
OFF, 32° – 482°F TRTMP11 = OFF
RTD Alarm Temperature OFF, 32° – 482°F ALTMP11 = OFF
RTD Trip Temperature
b
OFF, 32° – 482°F TRTMP12 = OFF
RTD Alarm
Temperature
b
OFF, 32° – 482°F ALTMP12 = OFF
Enable Winding Trip
Voting
Y, N
EWNDGV = N
Enable Bearing Trip
Voting
Y, N
EBRNGV = N
Enable RTD Biasing
Y, N
RTDBEN = Y
a
Note: When the TEMPREF setting equals C, the trip and alarm
temperature setting ranges above are: OFF, 0
° –
250°C.
b
The twelfth RTD input is only available when you use the
SIMPRO-100-RTD External RTD Module.
Summary of Contents for SIMPRO-100
Page 1: ...SIMPRO 100 Motor Protection Relay Instruction Manual Document No PRIM 2400C ...
Page 12: ...Contents SIMPRO 100 x PRIM 2400C ...
Page 16: ...Contents SIMPRO 100 xiv PRIM 2400C ...
Page 42: ...3 SIMPRO PC Software SIMPRO 100 40 PRIM 2400C ...
Page 100: ...6 ASCII Serial Port Operation SIMPRO 100 98 PRIM 2400C ...
Page 127: ...SIMPRO 100 Event Analysis 9 PRIM 2400C 125 Figure 9 2 Example SER Report ...
Page 136: ...10 Maintenance Troubleshooting SIMPRO 100 134 PRIM 2400C ...
Page 138: ...A Firmware Versions SIMPRO 100 136 PRIM 2400C ...
Page 206: ...D SIMPRO PC Compatibility Features SIMPRO 100 204 PRIM 2400C ...
Page 214: ...E Motor Thermal Element SIMPRO 100 212 PRIM 2400C ...
Page 230: ...F SIMPRO 100 Relay Settings Sheets SIMPRO 100 228 PRIM 2400C ...
Page 239: ......