4
Settings Calculation
SIMPRO-100
70
PRIM-2400C
Figure 4.7
Factory Contact Input Logic
Figure 4.8
Factory Event Triggering Logic
4.8
Serial Port Settings
The SIMPRO-100 Relay provides settings that
allow you to configure the communication
parameters for the front- and rear-panel serial
ports. The front-panel serial port only supports
ASCII communications described in detail in
Chapter 6, page 85. The rear-panel serial port
settings include the Protocol setting. When you
set the rear-panel serial port Protocol setting
equal to ASCII, the relay supports ASCII
commands at the rear-panel EIA-232 port. When
you set the rear-panel serial port Protocol setting
equal to MOD, the relay supports Modbus RTU
protocol at the rear-panel EIA-485 port and
disables the rear-panel EIA-232 port.
Table 4.40
SET P Serial Port Settings,
Protocol = ASCII
The SIMPRO-100 Relay front-panel serial port
supports EIA-232 communication of ASCII text
data and SEL Binary commands and responses.
The rear panel is equipped with EIA-232 and
EIA-485 serial port connectors. Table 4.40 shows
relay serial port settings for the front-panel port
and the rear-panel port when it is set to use
ASCII protocol. Set the Baud Rate, Data Bits,
Parity, and Stop Bits settings to match the serial
port configuration of the equipment that is
communicating with the serial port.
Setting Prompt
Setting Range
Setting Name =
Factory Default
Protocol, (shown
for rear port only)
ASCII, MOD
PROTO = ASCII
Baud Rate
300 – 19200
SPEED = 2400
Data Bits
7, 8
BITS = 8
Parity
O, E, N
PARITY = N
Stop Bits
1, 2
STOP = 1
Timeout
0 – 30 min
T_OUT = 15
Send Auto
Messages to Port
Y, N
AUTO = N
Enable Hardware
Handshaking
Y, N
RTSCTS = N
Fast Operate
Enable
Y, N
FASTOP = N
Summary of Contents for SIMPRO-100
Page 1: ...SIMPRO 100 Motor Protection Relay Instruction Manual Document No PRIM 2400C ...
Page 12: ...Contents SIMPRO 100 x PRIM 2400C ...
Page 16: ...Contents SIMPRO 100 xiv PRIM 2400C ...
Page 42: ...3 SIMPRO PC Software SIMPRO 100 40 PRIM 2400C ...
Page 100: ...6 ASCII Serial Port Operation SIMPRO 100 98 PRIM 2400C ...
Page 127: ...SIMPRO 100 Event Analysis 9 PRIM 2400C 125 Figure 9 2 Example SER Report ...
Page 136: ...10 Maintenance Troubleshooting SIMPRO 100 134 PRIM 2400C ...
Page 138: ...A Firmware Versions SIMPRO 100 136 PRIM 2400C ...
Page 206: ...D SIMPRO PC Compatibility Features SIMPRO 100 204 PRIM 2400C ...
Page 214: ...E Motor Thermal Element SIMPRO 100 212 PRIM 2400C ...
Page 230: ...F SIMPRO 100 Relay Settings Sheets SIMPRO 100 228 PRIM 2400C ...
Page 239: ......