SIMPRO-100 Relay Word and Corresponding TAR Command
6.8.41
TARGET R
(Level 1 or 2)
Resets front-panel tripping targets and releases
the trip signal if the fault
condition has vanished and no lockout conditions
are present. If the relay tripping targets do not
reset when you execute the
TARGET R
command at the relay serial port or use the
front-panel menu selection Reset Trip/Targets,
verify that the fault condition and all lockouts have
cleared.
6.8.42
TIME
(Level 1 or 2)
TIME
displays the relay clock. To set the clock,
type
TIME
and the desired setting, then press
<ENTER>
. Separate the hours, minutes, and
seconds with colons, semicolons, spaces,
commas, or slashes.
6.8.43
TRIGGER
(Level 1 or 2)
Use the
TRIGGER
command to generate an
event report. See Section 9.5, page 119 for more
information.
6.9
Serial Port Automatic
Messages
When the serial port AUTO setting is Y, the relay
sends automatic messages to indicate specific
conditions. The automatic messages are:
Table 6.20
Serial Port Automatic Messages
TAR
Relay Word Bits
1
STARTING
RUNNING
STOPPED
JAMTRIP
LOSSALRM
LOSSTRIP
46UBA
46UBT
2
49A
49T
THERMLO
NOSLO
TBSLO
ABSLO
*
*
3
50P1T
50P2T
50N1T
50N2T
50QT
50S
50G1T
50G2T
4
47T
TRGTR
START
52A
SPDSTR
SPEEDSW
RTDBIAS
RTDFLT
5
WDGALRM
WDGTRIP
BRGALRM
BRGTRIP
AMBALRM
AMBTRIP
OTHALRM
OTHTRIP
6
27P1
27P2
59P1
59P2
59G
81D1T
81D2T
81D3T
7
37PA
37PT
55A
55T
VARA
VART
*
*
8
LT1
LT2
LT3
LT4
RB1
RB2
RB3
RB4
9
SV1
SV2
SV3
SV4
SV1T
SV2T
SV3T
SV4T
10
IN1
IN2
IN3
IN4
IN5
IN6
IN7
*
11
TRIP
OUT1
OUT2
OUT3
ALARM
*
*
*
* Bit not used; reserved for future expansion.
a See Table 9.1 on page 117 for additional information on the meaning of each target LED condition.
Condition
Description
Power Up
The relay sends a message containing the
present date and time, relay and terminal
identifiers, and the Access Level 1 prompt
when the relay is turned on.
Event Trigger The relay sends an event summary each time
an event report is triggered (see Section 9.5,
Self-Test
Warning or
Failure
The relay sends a status report each time a
self-test warning or failure condition is
detected (see Section 6.8.36, page 95).
Summary of Contents for SIMPRO-100
Page 1: ...SIMPRO 100 Motor Protection Relay Instruction Manual Document No PRIM 2400C ...
Page 12: ...Contents SIMPRO 100 x PRIM 2400C ...
Page 16: ...Contents SIMPRO 100 xiv PRIM 2400C ...
Page 42: ...3 SIMPRO PC Software SIMPRO 100 40 PRIM 2400C ...
Page 100: ...6 ASCII Serial Port Operation SIMPRO 100 98 PRIM 2400C ...
Page 127: ...SIMPRO 100 Event Analysis 9 PRIM 2400C 125 Figure 9 2 Example SER Report ...
Page 136: ...10 Maintenance Troubleshooting SIMPRO 100 134 PRIM 2400C ...
Page 138: ...A Firmware Versions SIMPRO 100 136 PRIM 2400C ...
Page 206: ...D SIMPRO PC Compatibility Features SIMPRO 100 204 PRIM 2400C ...
Page 214: ...E Motor Thermal Element SIMPRO 100 212 PRIM 2400C ...
Page 230: ...F SIMPRO 100 Relay Settings Sheets SIMPRO 100 228 PRIM 2400C ...
Page 239: ......