SIMPRO-100
Control Equations & Relay Logic
B
PRIM-2400C
141
Table B.2
Relay Word Bit Definitions for SIMPRO-100
B.4
Control Equations
Control equations combine relay protection and
control elements with logic operators to create
custom protection and control schemes. This
section shows how to set the protection and
control elements (Relay Word bits) in the control
equations.
Control equations are set with combinations of
Relay Word bits to accomplish such functions as:
•
Tripping circuit breakers
•
Assigning contact inputs to functions
•
Operating contact outputs
You can use control equations to create
traditional or advanced custom schemes.
8
LT1
LT2
LT3
LT4
Control equation latch bit results.
RB1
RB2
RB3
RB4
Remote bits 1 – 4.
9
SV1
SV2
SV3
SV4
Control equation variables 1 – 4.
SV1T
SV2T
SV3T
SV4T
Control equation variable 1 – 4 with settable pickup and dropout time delay.
10
IN1
IN2
IN3
IN4
IN5
IN6
Contact inputs IN1 – IN6.
IN7
Contact input IN7. Available only when using SIMPRO-100-RTD External RTD module.
*
Reserved for future use.
11
TRIP
Contact outputs TRIP, OUT1, OUT2, OUT3, and ALARM.
OUT1
OUT2
OUT3
ALARM
*
*
*
Reserved for future use.
Row
Bit
Definition
Summary of Contents for SIMPRO-100
Page 1: ...SIMPRO 100 Motor Protection Relay Instruction Manual Document No PRIM 2400C ...
Page 12: ...Contents SIMPRO 100 x PRIM 2400C ...
Page 16: ...Contents SIMPRO 100 xiv PRIM 2400C ...
Page 42: ...3 SIMPRO PC Software SIMPRO 100 40 PRIM 2400C ...
Page 100: ...6 ASCII Serial Port Operation SIMPRO 100 98 PRIM 2400C ...
Page 127: ...SIMPRO 100 Event Analysis 9 PRIM 2400C 125 Figure 9 2 Example SER Report ...
Page 136: ...10 Maintenance Troubleshooting SIMPRO 100 134 PRIM 2400C ...
Page 138: ...A Firmware Versions SIMPRO 100 136 PRIM 2400C ...
Page 206: ...D SIMPRO PC Compatibility Features SIMPRO 100 204 PRIM 2400C ...
Page 214: ...E Motor Thermal Element SIMPRO 100 212 PRIM 2400C ...
Page 230: ...F SIMPRO 100 Relay Settings Sheets SIMPRO 100 228 PRIM 2400C ...
Page 239: ......