D
SIMPRO-PC Compatibility Features
SIMPRO-100
194
PRIM-2400C
D.3.1
A5B9 Fast Meter Status
Acknowledge Message
In response to the A5B9 request, the
SIMPRO-100 Relay clears the Fast Meter
(message A5D1) Status Byte. The SIMPRO-100
Relay Status Byte contains one active bit, STSET
(bit 4). The bit is set on power up and on settings
changes. If the STSET bit is set, the external
device should request the A5C1, A5C2, and
A5C3 messages. The external device can then
determine if the scale factors or line configuration
parameters have been modified.
In response to the A5CE request, the relay sends
the block shown in Table D.8.
Table D.8
A5CE Fast Operate Configuration Block
Table 0.1 A5CE Fast Operate Configuration Block
The SIMPRO-100 Relay performs the specified
remote bit operation if the following conditions are
true:
•
The Operate code is valid.
•
The Operate validation =
4 • Operate code + 1.
•
The message checksum is valid.
•
The FASTOP port setting is set to Y.
•
The relay is enabled.
Remote bit set and clear operations are latched
by the relay. Remote bit pulse operations assert
the remote bit for one processing interval
(1/4 cycle).
It is common practice to route remote bits to
output contacts to provide remote control of the
relay outputs. If you wish to pulse an output
contact closed for a specific duration, Siemens
recommends using the remote bit pulse
command and control equations to provide
secure and accurate contact control. The remote
device sends the remote bit pulse command; the
relay controls the timing of the output contact
assertion. You can use any remote bit and any
control equation timer to control any of the output
contacts.
Data
Description
A5CE
Command
18
Length
01
Support 1 circuit breaker or contactor
0004
Support 4 remote bit set/clear commands
0100
Allow remote bit pulse commands
31
Operate code, open breaker/contactor (STOP)
11
Operate code, close breaker/contactor (STR)
00
Operate code, clear remote bit RB1
20
Operate code, set remote bit RB1
40
Operate code, pulse remote bit RB1
01
Operate code, clear remote bit RB2
21
Operate code, set remote bit RB2
41
Operate code, pulse remote bit RB2
02
Operate code, clear remote bit RB3
22
Operate code, set remote bit RB3
42
Operate code, pulse remote bit RB3
03
Operate code, clear remote bit RB4
23
Operate code, set remote bit RB4
43
Operate code, pulse remote bit RB4
00
Reserved
checksum 1-byte checksum of all preceding bytes
Summary of Contents for SIMPRO-100
Page 1: ...SIMPRO 100 Motor Protection Relay Instruction Manual Document No PRIM 2400C ...
Page 12: ...Contents SIMPRO 100 x PRIM 2400C ...
Page 16: ...Contents SIMPRO 100 xiv PRIM 2400C ...
Page 42: ...3 SIMPRO PC Software SIMPRO 100 40 PRIM 2400C ...
Page 100: ...6 ASCII Serial Port Operation SIMPRO 100 98 PRIM 2400C ...
Page 127: ...SIMPRO 100 Event Analysis 9 PRIM 2400C 125 Figure 9 2 Example SER Report ...
Page 136: ...10 Maintenance Troubleshooting SIMPRO 100 134 PRIM 2400C ...
Page 138: ...A Firmware Versions SIMPRO 100 136 PRIM 2400C ...
Page 206: ...D SIMPRO PC Compatibility Features SIMPRO 100 204 PRIM 2400C ...
Page 214: ...E Motor Thermal Element SIMPRO 100 212 PRIM 2400C ...
Page 230: ...F SIMPRO 100 Relay Settings Sheets SIMPRO 100 228 PRIM 2400C ...
Page 239: ......