4
Settings Calculation
SIMPRO-100
66
PRIM-2400C
4.7
Output Configuration
4.7.1
Analog Output Settings
Table 4.34
Analog Output Settings
The SIMPRO-100 Relay provides a dc analog
current output with three signal ranges and a
variety of output parameters. Set the Analog
Output Signal Type to select the operating range
of dc output current. Select the Analog Output
Parameter from the list of available options.
When you select a percentage-type output
parameter, the relay automatically scales the
output to indicate full scale at 100%. If you select
a hottest RTD output parameter, the relay
automatically scales the output to indicate full
scale at 250°C or 482°F and zero scale at 0°C or
32°F. If you select average or maximum phase
current output parameters, the relay requests that
you enter your preferred Analog Output Full
Scale Current in secondary amps. The range
available depends on whether your nominal
secondary current is 5 A or 1 A. The Analog
Output Full Scale Current setting is hidden when
the Analog Output Parameter is not AVG_I or
MAX_I.
4.7.2
Front-Panel Configuration
Settings
Table 4.35
Front-Panel Configuration Settings
The relay default front-panel display shows
measured phase currents and, if included,
phase-to-phase voltage. When the relay is
equipped with voltage inputs, the Front-Panel
Power Display setting gives you the option to add
power quantities to the front-panel default display.
When Front-Panel Power Display is equal to Y,
the relay displays measured kW, horsepower,
kVAR, kVA, power factor, and frequency. When
the relay is equipped with internal or external
RTD inputs and the Front Panel RTD Display
setting equals Y, the relay displays the
temperatures of the hottest winding, bearing, and
other RTDs, plus the ambient temperature.
Use the Front-Panel Timeout setting as a security
measure. If the front-panel interface is inactive for
this length of time, the relay automatically blacks
out the front-panel display. This function
preserves the life of the vacuum fluorescent
display. If the display is within an Access Level 2
function such as relay setting entry, the function is
automatically terminated without saving changes.
If you prefer to disable the front-panel timeout
function during relay testing, set Front-Panel
Timeout equal to 0 minutes. Do not leave the
front-panel timeout setting at 0 minutes while the
relay is in service.
The Front-Panel Display Brightness setting
adjusts the intensity of the vacuum fluorescent
display. If the display dims over a period of years
or if the relay will be installed in a brightly lit
location, you may wish to increase the
Front-Panel Display Brightness setting.
Setting
Prompt
Setting Range
Setting Name =
Factory Default
Analog Output
Signal Type
0 – 1mA, 0 – 20mA,
4 – 20mA
AOSIG = 4 – 20mA
Analog Output
Parameter
%LOAD_I-Percentage of
Full Load Current
%THERM-Percentage
Thermal Capacity
WDG_RTD-Hottest
Winding RTD Temperature
BRG_RTD-Hottest
Bearing RTD Temperature
AVG_I-Average Phase
Current
MAX_I-Maximum Phase
Current
AOPARM =
%LOAD_I
Analog Output
Full Scale
Current
0.5 – 80.0 A ITAP = 5 A
0.1 – 16.0 A ITAP = 1 A
AOFSC = 5.0
Setting Prompt Setting Range
Setting Name =
Factory Default
Front Panel Power
Display
Y, N
FP_KW = N
Front Panel RTD
Display
Y, N
FP_RTD = N
Front Panel
Timeout
0-30 min
FP_TO = 15
Front Panel
Display Brightness
25%, 50%,
75%, 100%
FPBRITE = 50
Summary of Contents for SIMPRO-100
Page 1: ...SIMPRO 100 Motor Protection Relay Instruction Manual Document No PRIM 2400C ...
Page 12: ...Contents SIMPRO 100 x PRIM 2400C ...
Page 16: ...Contents SIMPRO 100 xiv PRIM 2400C ...
Page 42: ...3 SIMPRO PC Software SIMPRO 100 40 PRIM 2400C ...
Page 100: ...6 ASCII Serial Port Operation SIMPRO 100 98 PRIM 2400C ...
Page 127: ...SIMPRO 100 Event Analysis 9 PRIM 2400C 125 Figure 9 2 Example SER Report ...
Page 136: ...10 Maintenance Troubleshooting SIMPRO 100 134 PRIM 2400C ...
Page 138: ...A Firmware Versions SIMPRO 100 136 PRIM 2400C ...
Page 206: ...D SIMPRO PC Compatibility Features SIMPRO 100 204 PRIM 2400C ...
Page 214: ...E Motor Thermal Element SIMPRO 100 212 PRIM 2400C ...
Page 230: ...F SIMPRO 100 Relay Settings Sheets SIMPRO 100 228 PRIM 2400C ...
Page 239: ......