2 Parameters
2.2 List of parameters
SINAMICS DCM
128
List Manual (LH8), 02/2015, 6RX1800-0ED76
Note:
Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
Description:
Displays the effective control word 1 (STW1) of the drive for the master control.
Notice:
The master control only influences control word 1 and speed setpoint 1. Other control words/setpoints can be
transferred from another automation device.
Note:
OC: Operating condition
Description:
Sets the drive object number for communication via the field bus interface (USS).
Dependency:
Refer to: p0978
Note:
p2035 defines the destination for USS parameter requests (PIV).
p0978[0] defines the destination for USS process data (PZD).
The parameter is available globally on all drive objects.
The parameter is not influenced by setting the factory setting.
Description:
Sets the processing mode for PROFIdrive STW1.10 "master control by PLC".
Generally, control world 1 is received with the first receive word (PZD1) (this is in conformance to the PROFIdrive
profile). The behavior of STW1.10 = 0 corresponds to that of the PROFIdrive profile. For other applications that
deviate from this, the behavior can be adapted using this particular parameter.
Value:
0:
Freeze setpoints and continue to process sign-of-life
1:
Freeze setpoints and sign-of-life
2:
Do not freeze setpoints
Recommendation:
Do not change the setting p2037 = 0.
r2032
Master control control word effective / PcCtrl STW eff
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
Unsigned16
Dyn. index:
-
Func. diagram:
-
P-Group:
Displays, signals
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
ON/OFF1
Yes
No
-
01
OC / OFF2
Yes
No
-
02
OC / OFF3
Yes
No
-
03
Operation enable
Yes
No
-
04
Ramp-function generator enable
Yes
No
-
05
Start ramp-function generator
Yes
No
-
06
Speed setpoint enable
Yes
No
-
07
Acknowledge fault
Yes
No
-
08
Jog bit 0
Yes
No
3030
09
Jog bit 1
Yes
No
3030
10
Master ctrl by PLC
Yes
No
-
p2035
Fieldbus interface USS PIV drive object number / Fieldbus USS DO_no
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
Integer16
Dyn. index:
-
Func. diagram:
-
P-Group:
Communications
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
1 62
2
p2037
IF1 PROFIdrive STW1.10 = 0 mode / IF1 PD STW1.10=0
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Integer16
Dyn. index:
-
Func. diagram:
-
P-Group:
Communications
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 2
0
Summary of Contents for SINAMICS DCM
Page 1: ...s SINAMICS SINAMICS DCM List Manual 02 2015 Edition Answers for industry ...
Page 2: ......
Page 1192: ...A Appendix A 2 List of abbreviations SINAMICS DCM 1192 List Manual LH8 02 2015 6RX1800 0ED76 ...
Page 1202: ...Index SINAMICS DCM 1202 List Manual LH8 02 2015 6RX1800 0ED76 ...
Page 1203: ......