2 Parameters
2.2 List of parameters
SINAMICS DCM
162
List Manual (LH8), 02/2015, 6RX1800-0ED76
Description:
Sets the signal source for the connector-binector converter.
A PZD receive word can be selected as signal source. The signals are available to be serially passed-on
(interconnection).
Dependency:
Refer to: r2094, r2095
Note:
From the signal source set via the connector input, the corresponding lower 16 bits are converted.
p2099[0...1] together with r2094.0...15 and r2095.0...15 forms two connector-binector converters:
Connector input p2099[0] to binector output in r2094.0...15
Connector input p2099[1] to binector output in r2095.0...15
Description:
Sets the signal source for the connector-binector converter.
A PZD receive word can be selected as signal source. The signals are available to be serially passed-on
(interconnection).
Dependency:
Refer to: r2094, r2095
Note:
From the signal source set via the connector input, the corresponding lower 16 bits are converted.
p2099[0...1] together with r2094.0...15 and r2095.0...15 forms two connector-binector converters:
Connector input p2099[0] to binector output in r2094.0...15
Connector input p2099[1] to binector output in r2095.0...15
Description:
Selects the faults for which the fault response should be changed
Dependency:
The fault is selected and the required response is set under the same index.
Refer to: p2101
Note:
Re-parameterization is also possible if a fault is present. The change only becomes effective after the fault has been
resolved.
p2099[0...1]
CI: Connector-binector converter signal source / Con/bin S_src
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S, DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Integer16
Dyn. index:
-
Func. diagram:
2460, 2481
P-Group:
Communications
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0
p2099[0...1]
CI: Connector-binector converter signal source / Con/bin S_src
TM150, TM15DI_DO,
TM31
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Integer16
Dyn. index:
-
Func. diagram:
2468
P-Group:
Communications
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0
p2100[0...19]
Change fault response fault number / Chng resp F_no
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S, DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dyn. index:
-
Func. diagram:
8075
P-Group:
Messages
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 65535
0