2 Parameters
2.2 List of parameters
Description:
Displays the error (system deviation) between the setpoint and actual value of the technology controller.
Dependency:
Refer to: p2263
Description:
Sets the time constant for the differentiation (D component) of the technology controller.
Note:
p2274 = 0: Differentiation is disabled.
Description:
Sets the proportional gain (P component) of the technology controller.
Dependency:
Refer to: p2252
Note:
p2280 = 0: The proportional gain is disabled.
Description:
Sets the integral time (I component, integrating time constant) of the technology controller.
Dependency:
Refer to: p2252
Note:
p2285 = 0: The integral time is disabled.
Description:
Sets the signal source to hold the integrator for the technology controller.
r2273
CO: Technology controller error / Tec_ctrl error
DC_CTRL (Tech_ctrl),
DC_CTRL_R
(Tech_ctrl),
DC_CTRL_R_S
(Tech_ctrl),
DC_CTRL_S
(Tech_ctrl)
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
7958
P-Group:
Technology
Unit group:
9_1
Unit selection:
p0595
Not for motor type:
-
Scaling:
PERCENT
Expert list:
1
Min Max
Factory
setting
- [%]
- [%]
- [%]
p2274
Technology controller differentiation time constant / Tec_ctrl D comp T
DC_CTRL (Tech_ctrl),
DC_CTRL_R
(Tech_ctrl),
DC_CTRL_R_S
(Tech_ctrl),
DC_CTRL_S
(Tech_ctrl)
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
7958
P-Group:
Technology
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.000 [s]
60.000 [s]
0.000 [s]
p2280
Technology controller proportional gain / Tec_ctrl Kp
DC_CTRL (Tech_ctrl),
DC_CTRL_R
(Tech_ctrl),
DC_CTRL_R_S
(Tech_ctrl),
DC_CTRL_S
(Tech_ctrl)
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
7958
P-Group:
Technology
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.000 1000.000
1.000
p2285
Technology controller integral time / Tec_ctrl Tn
DC_CTRL (Tech_ctrl),
DC_CTRL_R
(Tech_ctrl),
DC_CTRL_R_S
(Tech_ctrl),
DC_CTRL_S
(Tech_ctrl)
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
7958
P-Group:
Technology
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.000 [s]
60.000 [s]
0.000 [s]
p2286[0...n]
BI: Hold technology controller integrator / Tec_ctr integ hold
DC_CTRL (Tech_ctrl),
DC_CTRL_R
(Tech_ctrl),
DC_CTRL_R_S
(Tech_ctrl),
DC_CTRL_S
(Tech_ctrl)
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dyn. index:
CDS, p0170
Func. diagram:
7958
P-Group:
Technology
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0
Summary of Contents for SINAMICS DCM
Page 1: ...s SINAMICS SINAMICS DCM List Manual 02 2015 Edition Answers for industry ...
Page 2: ......
Page 1192: ...A Appendix A 2 List of abbreviations SINAMICS DCM 1192 List Manual LH8 02 2015 6RX1800 0ED76 ...
Page 1202: ...Index SINAMICS DCM 1202 List Manual LH8 02 2015 6RX1800 0ED76 ...
Page 1203: ......