2 Parameters
2.2 List of parameters
SINAMICS DCM
188
List Manual (LH8), 02/2015, 6RX1800-0ED76
Description:
Sets the signal source for the pre-control signal of the technology controller.
Description:
Sets the maximum limit of the technology controller.
Dependency:
Refer to: p2292
Caution:
The maximum limit must always be greater than the minimum limit (p2291 > p2292).
Description:
Sets the minimum limit of the technology controller.
Dependency:
Refer to: p2291
Caution:
The maximum limit must always be greater than the minimum limit (p2291 > p2292).
Description:
Sets the ramping time for the output signal of the technology controller.
Dependency:
Refer to: p2291, p2292
Note:
The time refers to the set maximum and minimum limits (p2291, p2292).
p2289[0...n]
CI: Technology controller pre-control signal / Tec_ctr prectr_sig
DC_CTRL (Tech_ctrl),
DC_CTRL_R
(Tech_ctrl),
DC_CTRL_R_S
(Tech_ctrl),
DC_CTRL_S
(Tech_ctrl)
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
Unsigned32 / FloatingPoint32
Dyn. index:
CDS, p0170
Func. diagram:
7958
P-Group:
Technology
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
PERCENT
Expert list:
1
Min Max
Factory
setting
- -
0
p2291
CO: Technology controller maximum limiting / Tec_ctrl max_lim
DC_CTRL (Tech_ctrl),
DC_CTRL_R
(Tech_ctrl),
DC_CTRL_R_S
(Tech_ctrl),
DC_CTRL_S
(Tech_ctrl)
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
7958
P-Group:
Technology
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
PERCENT
Expert list:
1
Min Max
Factory
setting
-200.00 [%]
200.00 [%]
100.00 [%]
p2292
CO: Technology controller minimum limiting / Tec_ctrl min_lim
DC_CTRL (Tech_ctrl),
DC_CTRL_R
(Tech_ctrl),
DC_CTRL_R_S
(Tech_ctrl),
DC_CTRL_S
(Tech_ctrl)
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
7958
P-Group:
Technology
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
PERCENT
Expert list:
1
Min Max
Factory
setting
-200.00 [%]
200.00 [%]
0.00 [%]
p2293
Technology controller ramp-up/ramp-down time / Tec_ctr t_RU/RD
DC_CTRL (Tech_ctrl),
DC_CTRL_R
(Tech_ctrl),
DC_CTRL_R_S
(Tech_ctrl),
DC_CTRL_S
(Tech_ctrl)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
7958
P-Group:
Technology
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 [s]
100.00 [s]
1.00 [s]
Summary of Contents for SINAMICS DCM
Page 1: ...s SINAMICS SINAMICS DCM List Manual 02 2015 Edition Answers for industry ...
Page 2: ......
Page 1192: ...A Appendix A 2 List of abbreviations SINAMICS DCM 1192 List Manual LH8 02 2015 6RX1800 0ED76 ...
Page 1202: ...Index SINAMICS DCM 1202 List Manual LH8 02 2015 6RX1800 0ED76 ...
Page 1203: ......