2 Parameters
2.2 List of parameters
SINAMICS DCM
226
List Manual (LH8), 02/2015, 6RX1800-0ED76
Description:
Sets the scaling characteristic for the analog inputs of Terminal Module 31 (TM31).
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the x coordinate (input voltage in V or input current in mA) of the 2nd value pair of the
characteristic.
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Dependency:
The unit of this parameter (V or mA) depends on the analog input type.
Refer to: p4056
Notice:
This parameter is automatically overwritten when the analog input type (p4056) is modified.
Note:
The parameters for the characteristic do not have a limiting effect.
Description:
Sets the scaling characteristic for the analog inputs of Terminal Module 31 (TM31).
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the y coordinate (percentage) of the 2nd value pair of the characteristic.
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Notice:
This parameter is automatically overwritten when the analog input type (p4056) is modified.
Note:
The parameters for the characteristic do not have a limiting effect.
Description:
Sets the response threshold for wire-breakage monitoring of the analog inputs of Terminal Module 31 (TM31).
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Dependency:
For the following analog input type, the wire breakage monitoring is active:
p4056[x] = 3 (unipolar current input monitored (+4 mA ... +20 mA))
Refer to: p4056
p4059[0...1]
TM31 analog inputs characteristic value x2 / TM31 AI char x2
TM31
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
9566, 9568
P-Group:
Terminals
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
-20.000 20.000
10.000
p4060[0...1]
TM31 analog inputs characteristic value y2 / TM31 AI char y2
TM31
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
9566, 9568
P-Group:
Terminals
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
-1000.00 [%]
1000.00 [%]
100.00 [%]
p4061[0...1]
TM31 analog inputs wire breakage monitoring response threshold /
TM31 WireBrkThresh
TM31
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
9566, 9568
P-Group:
Terminals
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 [mA]
20.00 [mA]
2.00 [mA]