SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
237
2 Parameters
2.2 List of parameters
Dependency:
The simulation of a digital input is selected using p4095.
Refer to: p4095
Note:
This parameter is not saved when data is backed-up (p0971, p0977).
DI: Digital Input
DI/DO: Bidirectional Digital Input/Output
Description:
Sets the simulation mode for the analog inputs of Terminal Module 31 (TM31).
Value:
0:
Terminal evaluation for analog input x
1:
Simulation for analog input x
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Dependency:
The setpoint for the input voltage is specified via p4098.
Refer to: p4098
Note:
This parameter is not saved when data is backed-up (p0971, p0977).
AI: Analog Input
Description:
Sets the setpoint for the input value in simulation mode of the analog inputs of Terminal Module 31 (TM31).
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Dependency:
The simulation of an analog input is selected using p4097.
If AI x is parameterized as voltage input (p4056), then the setpoint is a voltage in V.
If AI x is parameterized as current input (p4056), then the setpoint is a current in mA.
Refer to: p4056, p4097
Note:
This parameter is not saved when data is backed-up (p0971, p0977).
AI: Analog Input
Description:
Sets the sampling time for the inputs and outputs of Terminal Module 15 (TM15).
Index:
[0] = TM15 input/output sampling time
08
DI/DO 8 (X541.2)
High
Low
-
09
DI/DO 9 (X541.3)
High
Low
-
10
DI/DO 10 (X541.4)
High
Low
-
11
DI/DO 11 (X541.5)
High
Low
-
p4097[0...1]
TM31 analog inputs simulation mode / TM31 AI sim_mode
TM31
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
Integer16
Dyn. index:
-
Func. diagram:
9566, 9568
P-Group:
Terminals
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 1
0
p4098[0...1]
TM31 analog inputs simulation mode setpoint / TM31 AI sim setp
TM31
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
9566, 9568
P-Group:
Terminals
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
-20.000 20.000
0.000
p4099[0]
TM15DI/DO inputs/outputs sampling time / TM15D I/O t_sampl
TM15DI_DO
Can be changed:
C1(3)
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
9399, 9400
P-Group:
Commands
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 [µs]
5000.00 [µs]
4000.00 [µs]