2 Parameters
2.2 List of parameters
SINAMICS DCM
248
List Manual (LH8), 02/2015, 6RX1800-0ED76
Description:
Display and connector output for the average value of each group for the Terminal Module 150 (TM150).
This value is calculated from the actual temperature values (r4105[0...11]) of each group.
Recommendation:
The following connector inputs can use these connector outputs for interconnection:
- CI: p0603
- CI: p0608[0...3]
- CI: p0609[0...3]
- CI: p2051
Index:
[0] = Group 0
[1] = Group 1
[2] = Group 2
Dependency:
Refer to: r4105, p4111, r4112, r4113
Note:
If one group is assigned sensor type "PTC" or "bimetal NC contact", then the average value -300 °C is output.
Description:
Sets the effect for an error of a sensor of a group for Terminal Module TM150 (TM150).
For p4117 = 0, the following applies:
The defective temperature sensor assigned to a group is not take into account when forming the group.
For p4117 = 1, the following applies:
For a sensor error, for the maximum value, minimum value and average value of the corresponding group, a value of
-300 °C is output.
Value:
0:
Skip sensor
1:
Output value = -300 °C
Index:
[0] = Group 0
[1] = Group 1
[2] = Group 2
Dependency:
Refer to: r4105, p4111, r4112, r4113, r4114
Description:
Sets the hysteresis for the fault threshold/alarm threshold (p4102[0...23]) for the Terminal Module 150 (TM150).
Index:
[0] = Temperature channel 0
[1] = Temperature channel 1
[2] = Temperature channel 2
[3] = Temperature channel 3
[4] = Temperature channel 4
[5] = Temperature channel 5
r4114[0...2]
CO: TM150 group temperature average actual value / TM150 grp temp av
TM150
Can be changed:
-
Calculated:
-
Access level:
1
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
9625
P-Group:
Terminals
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
p2006
Expert list:
1
Min Max
Factory
setting
- [°C]
- [°C]
- [°C]
p4117[0...2]
TM150 group sensor error effect / TM150 error effect
TM150
Can be changed:
U, T
Calculated:
-
Access level:
1
Data type:
Integer16
Dyn. index:
-
Func. diagram:
9625
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 1
0
p4118[0...11]
TM150 fault threshold/alarm threshold hysteresis / TM150 thresh hyst
TM150
Can be changed:
T
Calculated:
-
Access level:
1
Data type:
Unsigned16
Dyn. index:
-
Func. diagram:
9626, 9627
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 [K]
50 [K]
5 [K]