2 Parameters
2.2 List of parameters
SINAMICS DCM
254
List Manual (LH8), 02/2015, 6RX1800-0ED76
If the deviation is less than this limit, then the pulse number is not corrected. If it is higher than this limit, fault F3x131
is triggered.
If fault F3x131 is re-parameterized to alarm (A) or no message (N), the encoder pulses which have not been
corrected are added to the accumulator (p4688). The accumulator can be de-activated using p0437.7.
Dependency:
Refer to: p0437, p4688
Note:
This monitoring is activated by setting p0437.2 = 1 (position actual value correction).
The positive limit describes additional pulses due to EMC.
Description:
Sets the negative tolerance window in encoder pulses for limit 1 for the zero mark monitoring.
If the deviation is less than this limit, the PPR is not corrected. If it is higher than this limit, fault F3x131 is triggered.
If fault F3x131 is re-parameterized to alarm (A) or no message (N), the encoder pulses which have not been
corrected are added to the accumulator (p4688). The accumulator can be de-activated using p0437.7.
Dependency:
Refer to: p0437, p4681, p4688
Note:
This monitoring is activated by setting p0437.2 = 1 (position actual value correction).
For a set value = -1001, the negated value of p4681 is effective.
The negative limit describes the pulses lost due to a covered glass panel in the incremental encoder.
Description:
Sets the positive tolerance window in encoder pulses for limit 2 for the zero mark monitoring.
If the zero mark deviation is higher than the tolerance set in p4681 and p4682 and fault F3x131 is re-parameterized
to alarm (A) or no message (N), the accumulator p4688 is compared with this parameter and, if applicable, alarm
A3x422 is output for 5 seconds.
Dependency:
Refer to: p0437, p4681, p4682, p4688
Note:
Zero mark monitoring is activated by setting p0437.2 = 1 (position actual value correction).
Description:
Sets the negative tolerance window in encoder pulses for limit 2 for the zero mark monitoring.
If the zero mark deviation is higher than the tolerance set in p4681 and p4682 and fault F3x131 is re-parameterized
to alarm (A) or no message (N), the accumulator p4688 is compared with this parameter and, if applicable, alarm
A3x422 is output for 5 seconds.
Dependency:
Refer to: p0437, p4683, p4688
Note:
Zero mark monitoring is activated by setting p0437.2 = 1 (position actual value correction).
For a set value = -100001, the negated value of p4683 is effective.
p4682[0...n]
Zero mark monitoring tolerance window limit 1 negative / ZM tol lim 1 neg
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed:
C2(4)
Calculated:
-
Access level:
3
Data type:
Integer32
Dyn. index:
EDS, p0140
Func. diagram:
-
P-Group:
Encoder
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
-1001 0
-1001
p4683[0...n]
Zero mark monitoring tolerance window alarm threshold positive / ZM tol A_thr pos
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed:
C2(4)
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dyn. index:
EDS, p0140
Func. diagram:
-
P-Group:
Encoder
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 100000
0
p4684[0...n]
Zero mark monitoring tolerance window alarm threshold negative / ZM tol A_thr neg
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed:
C2(4)
Calculated:
-
Access level:
3
Data type:
Integer32
Dyn. index:
EDS, p0140
Func. diagram:
-
P-Group:
Encoder
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
-100001 0
-100001