2 Parameters
2.2 List of parameters
SINAMICS DCM
436
List Manual (LH8), 02/2015, 6RX1800-0ED76
Description:
Sets the response to setpoint inversion on the ramp-function generator.
Value:
0:
Hard setpoint change
1:
Soft setpoint change
Note:
If p50295 = 0:
In the event of setpoint inversion during ramping up, ramp-up is aborted and ramp-down initial rounding commences
immediately, and vice versa. As the setpoint is not increased (decreased) any further, the signal at the ramp-function
generator output has a breakpoint (in other words, there is a step change in the acceleration rate).
If p50295 = 1:
In the event of setpoint inversion during ramping up, ramp-up is slowly switched over to ramp-down, and vice versa.
The setpoint increases/decreases further. There is no breakpoint in the signal at the ramp-function generator output
(in other words, there is no step change in the acceleration rate).
Description:
Sets the ramp-down time for quick stop (OFF3) on the ramp-function generator.
When the "Quick stop" command is sent, the drive is decelerated to zero speed at the current limit.
However, if this is not permissible or desirable for mechanical reasons, a value > 0 must be set in this parameter. The
drive will then decelerate along the down ramp set here.
Description:
Sets the initial rounding for quick stop (OFF3) on the ramp-function generator.
Description:
Sets the final rounding for quick stop (OFF3) on the ramp-function generator.
p50295[0...n]
Transition rounding operating mode / RFG rounding mode
DC_CTRL
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
Integer16
Dyn. index:
DDS, p0180
Func. diagram:
3152
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 1
0
p50296[0...n]
RFG quick stop (OFF3) ramp-down time / RFG OFF3 t_ramp-dn
DC_CTRL
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
3150
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 [s]
650.00 [s]
0.00 [s]
p50297[0...n]
RFG quick stop (OFF3) initial rounding / RFG OFF3 init rndg
DC_CTRL
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
3150
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 [s]
100.00 [s]
0.00 [s]
p50298[0...n]
RFG quick stop (OFF3) final rounding / RFG OFF3 fin rndg
DC_CTRL
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
3150
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 [s]
100.00 [s]
0.00 [s]