Dependency:
The setting value for the ramp-function generator output is selected via binector input p50640.
p50640 = 0 signal:
If the machine is not running, the value supplied via connector input p50639[1] is accepted.
p50640 = 1 signal:
The value supplied via connector input p50639[0] is accepted as the setting value.
Refer to: p50640
Description:
Sets the signal source for accepting the setting value of the ramp-function generator.
Dependency:
Refer to: p50639
Description:
Sets the signal source for "Bypass ramp-function generator".
Note:
The "Bypass ramp-function generator" signal can also be set via binector input p50649[0 to 2].
Description:
Sets the signal source for variable positive limiting of the main setpoint.
Notice:
Negative values at the selected parameters generate a negative maximum value at the limiting output.
Note:
The minimum of the values set via index 0 to 3 is applied as the limit.
Description:
Sets the signal source for variable positive limiting of the main setpoint.
Notice:
Positive values at the selected parameters generate a positive minimum value at the limiting output.
Note:
The maximum of the values set via index 0 to 3 is applied as the limit.
p50640[0...n]
BI: RFG signal source for accepting setting value / RFG accept set v
DC_CTRL
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dyn. index:
CDS, p0170
Func. diagram:
3152
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0
p50641[0...n]
BI: Bypass ramp-function generator signal source / Bypass RFG sig s
DC_CTRL
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dyn. index:
CDS, p0170
Func. diagram:
3152
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0
p50642[0...3]
CI: Setpoint processing sig source for pos limiting of main setpoint / M set lim p sig s
DC_CTRL
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / FloatingPoint32
Dyn. index:
-
Func. diagram:
3135
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
PERCENT
Expert list:
1
Min Max
Factory
setting
- -
52002[0]
p50643[0...3]
CI: Setpoint processing sig source for neg limiting of main setpoint / M set lim n sig s
DC_CTRL
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / FloatingPoint32
Dyn. index:
-
Func. diagram:
3135
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
PERCENT
Expert list:
1
Min Max
Factory
setting
- -
[0]
52184[0]
[1] 52185[0]
[2] 52186[0]
[3] 52187[0]
Summary of Contents for SINAMICS DCM
Page 1: ...s SINAMICS SINAMICS DCM List Manual 02 2015 Edition Answers for industry ...
Page 2: ......
Page 1192: ...A Appendix A 2 List of abbreviations SINAMICS DCM 1192 List Manual LH8 02 2015 6RX1800 0ED76 ...
Page 1202: ...Index SINAMICS DCM 1202 List Manual LH8 02 2015 6RX1800 0ED76 ...
Page 1203: ......