SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
529
2 Parameters
2.2 List of parameters
Description:
Setting to reset the operating hours of the device fan that have accumulated.
Value:
0:
Inactive
1:
Reset
Index:
[0] = Fan terminal XV1
[1] = Fan terminal XV2
[2] = Fan terminal XV3
[3] = Fan terminal XV4
[4] = Fan ON
Dependency:
Refer to: r50960, p50961
Note:
Procedure to reset the operating hours:
Set p50962[x] = 1
The parameter is automatically set to zero after this is done.
Description:
Behavior of the fan control:
0 : The fan control takes into account the temperature sensor.
1 : The fan control does not take into account the temperature sensor.
Value:
0:
The fan control takes into account the temperature sensor.
1:
The fan control doesn't take into account the temperature sensor
Dependency:
Refer to: r50960, p50961
Note:
Setting 1:
The fan is only switched off after the parameterized fan run-on time, independent of the various temperature
measurements and independent of the calculated thyristor temperature rise (=barrier layer temperature of the
thyristors).
As a consequence, it is also possible to acknowledge a fan fault even at ambient temperatures > 35°.
Description:
Sets the signal sources for the binector inputs on the binector-connector converter.
Dependency:
Refer to: r52620
p50962[0...4]
Device fan reset operating hours / Dev_fan reset h
DC_CTRL
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
Integer16
Dyn. index:
-
Func. diagram:
8045
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 1
0
p50963
Behavior of the fan control / Behavior fan ctrl
DC_CTRL
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
Integer16
Dyn. index:
-
Func. diagram:
8047
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 1
0
p51117[0...15]
BI: Binector-connector converter signal source / Bin/con sig s
DC_CTRL
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
Unsigned32 / Binary
Dyn. index:
-
Func. diagram:
9300
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0