2 Parameters
2.2 List of parameters
SINAMICS DCM
540
List Manual (LH8), 02/2015, 6RX1800-0ED76
Description:
Sets the signal source for the connectors to be recorded by the recorder function.
Dependency:
Refer to: p51701, p51702, p51703, p51704, p51705, p51706
Note:
[0] = Signal source for the first connector to be recorded
[1] = Signal source for the second connector to be recorded
Description:
Sets the signal source for the binectors to be recorded by the recorder function.
Dependency:
Refer to: p51700, p51702, p51703, p51704, p51705, p51706
Note:
[0] = Signal source for the first binector to be recorded
[1] = Signal source for the second binector to be recorded
Description:
Setting to select the channels to be recorded.
Dependency:
Refer to: p51700, p51701, p51703, p51704, p51705, p51706
Description:
Sets the recording interval,
during which the signals selected with the channel selection parameters (p51702.0 to 3) are scanned and saved
internally.
Dependency:
Refer to: p51700, p51701, p51702, p51704, p51705, p51706
p51700[0...1]
CI: Signal source for connector recorder function / Rec fct con sig s
DC_CTRL
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
Unsigned32 / FloatingPoint32
Dyn. index:
-
Func. diagram:
8050
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
PERCENT
Expert list:
1
Min Max
Factory
setting
- -
0
p51701[0...1]
BI: Signal source for binector recorder function / Rec fct bin sig s
DC_CTRL
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
Unsigned32 / Binary
Dyn. index:
-
Func. diagram:
8050
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0
p51702
Recorder function channel selection / Rec fct sel
DC_CTRL
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
Unsigned32
Dyn. index:
-
Func. diagram:
8050
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
1111
bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Channel 0
Active
Not active
-
01
Channel 1
Active
Not active
-
02
Channel 2
Active
Not active
-
03
Channel 3
Active
Not active
-
p51703
Recorder function recording interval / Rec fct t_rec
DC_CTRL
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
Unsigned32
Dyn. index:
-
Func. diagram:
8050
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
1 [s]
1000 [s]
1 [s]