2 Parameters
2.2 List of parameters
SINAMICS DCM
636
List Manual (LH8), 02/2015, 6RX1800-0ED76
Dependency:
Refer to: p51832, p51833, p51834, p51835
Refer to: A60266, F60267
Description:
Displays the state of the line for armature and field.
Description:
Display and connector output for the state of the thyristors.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Fan ON
ON
OFF
-
01
Fan ON inverted
ON
OFF
-
02
Fan relay status
Switched on
Switched off
-
03
External fault
Yes
No
-
04
External fault inverted
Yes
No
-
r53145.0...13
CO/BO: Line state / Line state
DC_CTRL
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
Unsigned16
Dyn. index:
-
Func. diagram:
6950, 6954
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Armature supply system overvoltage
Yes
No
-
01
Armature supply system undervoltage
Yes
No
-
02
Armature supply system overfrequency
Yes
No
-
03
Armature supply system underfrequency
Yes
No
-
04
Armature supply system phase failure
Yes
No
-
05
Field supply system overvoltage
Yes
No
-
06
Field supply system undervoltage
Yes
No
-
07
Field supply system overfrequency
Yes
No
-
08
Field supply system underfrequency
Yes
No
-
09
Field supply system phase failure
Yes
No
-
10
Armature supply system OK
Yes
No
-
11
Field supply system OK
Yes
No
-
12
Phase rotating clockwise
Yes
No
-
13
Line symmetry
Yes
No
-
r53146.0...13
CO/BO: Thyristor state / Thyr state
DC_CTRL
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dyn. index:
-
Func. diagram:
6950
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Thyristor X11 conducting
Yes
No
-
01
Thyristor X12 conducting
Yes
No
-
02
Thyristor X13 conducting
Yes
No
-
03
Thyristor X14 conducting
Yes
No
-
04
Thyristor X15 conducting
Yes
No
-
05
Thyristor X16 conducting
Yes
No
-
08
Thyristor X21 conducting
Yes
No
-
09
Thyristor X22 conducting
Yes
No
-
10
Thyristor X23 conducting
Yes
No
-
11
Thyristor X24 conducting
Yes
No
-
12
Thyristor X25 conducting
Yes
No
-
13
Thyristor X26 conducting
Yes
No
-