4 Faults and alarms
4.2 List of faults and alarms
Remedy:
- Switch off the power supply of the specified DRIVE-CLiQ component and switch it on again.
- For SINUMERIK, auto commissioning is prevented. In this case, a POWER ON is required for all components and
the auto commissioning must be restarted.
F01010
Drive type unknown
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
An unknown drive type was found.
Fault value (r0949, interpret decimal):
Drive object number (refer to p0101, p0107).
Remedy:
- replace Power Module.
- carry out a POWER ON (power off/on) for all components.
- upgrade firmware to later version.
- contact the Hotline.
F01011 (N)
Download interrupted
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The project download was interrupted.
Fault value (r0949, interpret decimal):
1: The user prematurely interrupted the project download.
2: The communication cable was interrupted (e.g. cable breakage, cable withdrawn).
3: The project download was prematurely ended by the commissioning software (e.g. STARTER, SCOUT).
100: Different versions between the firmware version and project files which were loaded by loading into the file
system "Download from memory card".
Note:
The response to an interrupted download is the state "first commissioning".
Remedy:
- check the communication cable.
- download the project again.
- boot from previously saved files (power-down/power-up or p0976).
- when loading into the file system (download from memory card), use the matching version.
Reaction upon N:
NONE
Acknowl. upon N:
NONE
F01015
Internal software error
Message value:
%1
Message class:
Hardware / software error (1)
Drive object:
All objects
Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
An internal software error has occurred.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- carry out a POWER ON (power off/on) for all components.
- upgrade firmware to later version.
- contact the Hotline.