Commissioning
5.3 Preparing for commissioning
SINAMICS G115D distributed drive
Operating Instructions, 12/2020, FW V4.7 SP13, A5E48681219B-002
103
5.3.2
Collecting motor data
G115D converter with SIMOGEAR geared motor
If you use a G115D converter with SIMOGEAR geared motor, you do not need to input
specific motor data since all necessary motor data is pre-configured in the factory.
For more information about the detailed motor data, refer to the following section:
Rating plate for geared motors with SINAMICS G115D Motor Mounted (Page 399)
G115D wall-mounted converter
For a G115D wall-mounted converter, if you use a SIMOGEAR geared motor for SINAMICS
G115D, you only need to specify the article number of the motor in the commissioning tool
(Startdrive or SINAMICS G120 Smart Access); otherwise, you must enter the data shown on
the motor rating plate.
Data for a SIMOGEAR geared motor
Rating plate for geared motors with SINAMICS G115D Wall Mounted (Page 400)
Pay attention to the connection of the motor (star connection [Y] or delta connectio
n [Δ] ).
Note the appropriate motor data for connecting.
Data for a standard asynchronous motor
Before starting commissioning, you must know the following data:
•
Which motor is connected to the converter?
Note down the article number of the motor on the motor rating plate.
If available, note down the motor code on the motor rating plate.
See below for an example of the rating plate for a standard asynchronous motor: