Advanced commissioning
6.6 Drive control via Ethernet/IP
SINAMICS G115D distributed drive
Operating Instructions, 12/2020, FW V4.7 SP13, A5E48681219B-002
151
No. Service
Type
Name
Value/explanation
6
get
UINT32 Serial number
bits 0 … 19: consecutive number;
bits 20 … 23: Production identifier
bits 24 … 27: Month of manufacture (0 = Jan, B = Dec)
Bits 28 … 31: Year of manufacture (0 = 2002)
7
get
Short
String
Product name
Max. length 32 bytes
Explanation of No. 5 of the previous table
Byte Bit
Name
Description
1
0
Owned
0: Converter is not assigned to any master
1: Converter is assigned to a master
1
Reserved
2
Configured
0: Ethernet/IP basic settings
1: Modified Ethernet/IP settings
For G120, always = 1
3
Reserved
4 … 7
Extended Device
Status
0: Self-test or status not known
1: Firmware update active
2: At least one I/O connection with error
3: No I/O connections
4: Incorrect configuration in the ROM
5: Fatal fault
6: At least one I/O connection is active
7: All I/O connections in the quiescent state
8 … 15: Reserved
2
8 … 11
Not used
12 … 15
Reserved
Assembly Object, Instance Number: 4 hex
Supported services
Class
•
Get Attribute single
Instance •
Get Attribute single
•
Set Attribute single
Class Attribute
No. Service
Type
Name
1
get
UINT16
Revision
2
get
UINT16
Max Instance
3
get
UINT16
Num of Instances
Instance Attribute
No. Service
Type
Name
Value/explanation
3
set
Array of UINT8 Assembly
1 byte array
Supported ODVA AC/DC assemblies
(Page 160)