Advanced commissioning
6.9 Conveyor technology control functions (for G115D PROFINET and AS-
i variants only)
SINAMICS G115D distributed drive
196
Operating Instructions, 12/2020, FW V4.7 SP13, A5E48681219B-002
•
With the end position shutdown activated (p3392 = 1), the following applies:
–
If the motor runs in positive direction, it stops only when the stop sensor positive
direction (p3384) is triggered.
–
If the motor runs in negative direction, it stops only when the stop sensor negative
direction (p3385) is triggered.
–
A new ON command must be initiated to start the motor again and the new movement
is only possible in the opposite direction.
–
Setting the sensor bypass signal (p3390) to 1 does not override the stop sensor signals
p3384 and p3385.
Note
With the end position shutdown (p3392 = 1) and level-triggered sensor signals (p3394 = 1 or
2) activated, once a stop sensor is triggered, the motor stops even if the level is canceled.