Advanced commissioning
6.15 Setpoints
SINAMICS G115D distributed drive
234
Operating Instructions, 12/2020, FW V4.7 SP13, A5E48681219B-002
Parameters
Table 6- 1
Basic settings
Parameter
Description
Setting
p1035[0...n] BI: Motorized potentiometer set-
point higher
Signal source to continuously increase the set-
point
The factory setting depends on the converter.
•
With PROFINET interface: [0] 2090.13; [1] 0
•
Without PROFINET interface: 0
p1036[0...n] BI: Motorized potentiometer set-
point lower
Signal source to continuously decrease the set-
point
The factory setting depends on the converter.
•
With PROFINET interface: [0] 2090.14; [1] 0
•
Without PROFINET interface: 0
p1040[0...n] Motorized potentiometer start
value [rpm]
Start value that is effective when the motor is
switched on.
Factory setting: 0 rpm
p1047
Motorized potentiometer, ramp-
up time [s]
MOP ramp-up time
Factory setting: 10 s
p1048
Motorized potentiometer, ramp-
down time [s]
MOP ramp-down time
Factory setting: 10 s
r1050
Motorized potentiometer, setpoint
after the ramp-function generator
Motorized potentiometer, setpoint after the
ramp-function generator
p1070[0...n] CI: Main setpoint
Signal source for the main setpoint
The factory setting depends on the converter.
•
With PROFINET interface: [0] 2050[1]
•
Without PROFINET interface: [0] 755[0]
p1071[0...n] CI: Main setpoint scaling
Signal source for scaling the main setpoint
Factory setting: 1
r1073
CO: Main setpoint active
Displays the active main setpoint
p1075[0...n] CI: Supplementary setpoint
Signal source for the supplementary setpoint
Factory setting: 0
p1076[0...n] CI: Supplementary setpoint scaling Signal source for scaling the supplementary set-
point
Factory setting: 0
r1077
CO: Supplementary setpoint effec-
tive [rpm]
Displays the effective supplementary setpoint.
The value shown is the additional setpoint after
scaling.