Wiring
4.14 Connecting to AS-i
SINAMICS G115D distributed drive
Operating Instructions, 12/2020, FW V4.7 SP13, A5E48681219B-002
93
3. Press the
button until you reach the required number.
By pressing both the
and
simultaneously, you can toggle between A and B
identifiers of the address.
4. Press the
button to accept this number.
ProG
is displayed briefly.
Both of the numbers allocated to the slaves are now displayed in the
lower part of the screen.
Changing existing addresses of the AS-i slaves
If the allocated addresses used two different numbers, for example, 10A and 11A, then if one
of the slave addresses is reset to 0 the other slave is not affected.
If the allocated addresses use the same number, for example, 20A and 20B, then if one slave
address is reset to 0, then both slave numbers will be reset to 0.
Modifying an existing address of a single slave within the converter will not affect the address
of the other slave.
To change an existing address of a slave, the following procedure should be performed:
1. Plug the AS-i Programmer into the addressing socket (interface X03) of the converter.
2. Turn the dial on the Programmer to the
ADDR
position. The display
will indicate that this mode has been selected.
3. Press the
button; the screen will display
uSE
and the number
of the lower addressed slave.
The existing slave addresses are shown at the bottom of the display.
4. Press the
and
buttons to select the slave address number to be changed.
5. Press the
button; the display now shows
SEt
.
The selected number will begin to flash.
6. Press the
and
buttons to select the new slave address
number.
7. Press the
button to confirm the new address.
ProG
is displayed briefly followed by confirmation of the address
change.
Further information on the operation as Ethernet nodes can be found in the Function Manual
"Fieldbuses".
Overview of the manuals (Page 542)