11/03
Diagnosis / Faults and Alarms
SINAMICS G150
Operating Manual
10-43
Reaction: OFF2
Cause:
Failure in 24V power supply for power section.
- Below the 16 V threshold for longer than 3 ms.
Remedy:
Check 24V DC voltage of power section.
Acknowl.: POWER
ON
F30801
Power section DRIVE-CLiQ: Sign of life missing
Reaction: OFF2
Cause:
DRIVE-CLiQ communication between control unit and affected power section defective.
Remedy:
- Check cabinet design and cabling for EMC conformity.
- Replace affected component.
See also: p9916
Acknowl.: Immediate
F30805
Power section: Checksum EPROM not correct
Reaction: OFF2
Cause:
Internal parameter data damaged
Remedy:
Replace module
Acknowl.: Immediate
F30808
Power section: Power ON required
Reaction: OFF2
Cause:
When a project is downloaded to a drive that has been put into operation, the power must be
switched on.
Remedy:
POWER ON for all components (switch off/on).
Acknowl.: POWER
ON
F30820 -
F30825
Power section DRIVE-CLiQ: Telegram faulted
Reaction: OFF2
Cause:
DRIVE-CLiQ communication between control unit and affected power section defective.
Remedy:
- Check cabinet design and cabling for EMC conformity.
- Replace affected component.
See also: p9916
Acknowl.: Immediate
F30826
F30827
Power section DRIVE-CLiQ: fault in cyclic data transfer
Reaction: OFF2
Cause:
DRIVE-CLiQ communication between control unit and affected power section defective.
Remedy:
- Check firmware states of affected components.
- Replace Control Unit.
Acknowl.: Immediate
F30828
Power section DRIVE-CLiQ: Receive ALARM bit
Reaction: OFF2
Cause:
DRIVE-CLiQ communication between control unit and affected power section defective.
Remedy:
Replace affected component.
Acknowl.: Immediate
F30829
F30830
Power section DRIVE-CLiQ: fault in cyclic data transfer
Reaction: OFF2
Cause:
DRIVE-CLiQ communication between control unit and affected power section defective.
Remedy:
- Check firmware states of affected components.
- Replace affected component.
See also: p9916
Acknowl.: Immediate
F30831
Power section DRIVE-CLiQ: Telegram faulted
Summary of Contents for SINAMICS G150
Page 2: ......
Page 22: ...Device Overview 11 03 SINAMICS G150 2 10 Operating Manual ...
Page 196: ...Diagnosis Faults and Alarms 11 03 SINAMICS G150 10 54 Operating Manual ...
Page 208: ...Maintenance and Servicing 11 03 SINAMICS G150 11 12 Operating Manual ...
Page 234: ......
Page 238: ...Parameterlist 11 03 SINAMICS G150 Parameterlist 4 Operating Manual ...
Page 239: ......