Device Overview
11/03
SINAMICS G150
2-8
Operating Manual
Type Plate Data (from Type Plate on Previous Page)
Table 2-2
Type plate data
Specification Value
Explanation
Input
3AC
380 – 480 V
239 A
Three-phase connection
Rated input voltage
Rated input current
Output
3AC
0 – 480 V
210 A
Three-phase connection
Rated output voltage
Rated output current
Temperature range
0 -40 °C
Ambient temperature range within which the cabinet unit can
operate under 100 % load
Degree of protection
IP20
Degree of protection
Duty class
I
I: Duty class I to EN 60146-1-1 = 100 % (continuously)
(with the specified current values, the cabinet unit can operate
continuously under 100 % load)
Cooling method
AF
A: coolant: air
F: circulation method: forced cooling, drive unit (fan) in the
device
Weight
Weight of the cabinet unit
Explanation of the Option Short Codes
Table 2-3
Explanation of the option codes
Version
A
C
Input options
L00
Radio interference suppression filter, limit class A1 (TN, TT systems)
•
−
L13
Main contactor (for currents < 800 A)
•
−
L22
Without line reactor in power range P < 500 kW (available soon)
•
•
L23
Line reactor u
k
= 2 % for P > 500 kW
•
•
L26
Main circuit-breaker (incl. fuses/circuit-breakers)
•
−
Output options
L08 Output
filter
•
−
Input and output options
M70
EMC shield bus
•
•
M75 PE
busbar
•
•
Summary of Contents for SINAMICS G150
Page 2: ......
Page 22: ...Device Overview 11 03 SINAMICS G150 2 10 Operating Manual ...
Page 196: ...Diagnosis Faults and Alarms 11 03 SINAMICS G150 10 54 Operating Manual ...
Page 208: ...Maintenance and Servicing 11 03 SINAMICS G150 11 12 Operating Manual ...
Page 234: ......
Page 238: ...Parameterlist 11 03 SINAMICS G150 Parameterlist 4 Operating Manual ...
Page 239: ......