Technical Data
11/03
SINAMICS G150
12-14
Operating Manual
Table 12-15 Version A, 660 V – 690 V, part 4
Category Unit
Order no.
6SL3710-
1GH34-7AA0 1GH35-8AA0 1GH37-4AA0
Rated motor output
kW
450
560
710
Rated connection voltage
V
3 AC 660 V to 690 V ±10 % (-15 % < 1 min)
Rated input current
A
493
608
774
Rated output current
A
465
575
735
Base load current
A
452
560
710
Power loss
kW
9.1
10.8
13.5
Cooling air requirement
m³/s
0.78
0.78
1.48
Sound pressure level at 50/60
Hz
dB(A) 72/75
72/75
72/75
Power connection
Recommended: DIN VDE
AWG / MCM
Maximum: DIN VDE
AWG / MCM
Fastening screw
mm
2
mm
2
2 x 185
2 x (500)
4 x 240
4 x (600)
M12 (2 holes)
2 x 240
2 x (600)
4 x 240
4 x (600)
M12 (2 holes)
3 x 185
3 x (500)
8 x 240
8 x (600)
M12 (4 holes)
Motor connection
Recommended: DIN VDE
AWG / MCM
Maximum: DIN VDE
AWG / MCM
Fastening screw
mm
2
mm
2
2 x 185
2 x (500)
4 x 240
4 x (600)
M12 (2 holes)
2 x 240
2 x (600)
4 x 240
4 x (600)
M12 (2 holes)
3 x 185
3 x (500)
6 x 240
6 x (600)
M12 (3 holes)
Protective earth connection
Fastening screw
M12 (2 holes)
M12 (2 holes)
M12 (18 holes)
Approx. weight (standard
version)
kg 860
860
1320
Dimensions (w x h x d)
mm
1200 x 2000 x 600 1200 x 2000 x 600 1600 x 2000 x 600
Recommended protection
Conductor protection
(with option L26)
Rated current
Size to DIN 43 620-1
Cond./semi-cond. protection
(without option L26)
Rated current
Size to DIN 43 620-1
A
A
3NA3 352-6
2 x 315
2
3NE1 435-2
560
3
3NA3 354-6
2 x 355
3
3NE1 447-2
670
3
3NA3 365-6
2 x 500
3
3NE1 448-2
850
3
Summary of Contents for SINAMICS G150
Page 2: ......
Page 22: ...Device Overview 11 03 SINAMICS G150 2 10 Operating Manual ...
Page 196: ...Diagnosis Faults and Alarms 11 03 SINAMICS G150 10 54 Operating Manual ...
Page 208: ...Maintenance and Servicing 11 03 SINAMICS G150 11 12 Operating Manual ...
Page 234: ......
Page 238: ...Parameterlist 11 03 SINAMICS G150 Parameterlist 4 Operating Manual ...
Page 239: ......