4.9.5 Cabinet
Illumination
with Service Socket (Option L50)
Description
One universal lamp with an integrated service socket is installed for each cabinet
panel. The power supply for the cabinet illumination and socket must be provided
externally and fused at max. 10 A. The cabinet illumination is switched on manually
via a slide switch or automatically by means of an integrated motion detector. The
mode is switch-selected.
Connection
Table 4-20
Terminal block X390 – connection for cabinet illumination with service socket
Terminal Designation
Technical
data
1 L1
2 N
3 PE
230 V AC
Max. connectable cross-section: 4 mm² (AWG 10)
4.9.6 Cabinet
Anti-Condensation Heating (Option L55)
Description
The anti-condensation heating is used at low ambient temperatures and high levels
of humidity to prevent condensation forming.
A 100-W heater is installed for a 400 mm and 600 mm cabinet panel, and 2 100-W
heaters for an 800/1000 and 1200 mm cabinet panel. The power supply for the
heating (110 V – 230 V AC) must be provided externally and fused at max. 16 A.
Connection
Table 4-21
Terminal block X240 – connection for cabinet anti-condensation heating
Terminal Designation
Technical
data
1 L1
2 N
110 V -230 V AC
power supply
3 PE
Protective
conductor
Max. connectable cross-section: 4 mm² (AWG 10)
Summary of Contents for SINAMICS G150
Page 2: ......
Page 22: ...Device Overview 11 03 SINAMICS G150 2 10 Operating Manual ...
Page 196: ...Diagnosis Faults and Alarms 11 03 SINAMICS G150 10 54 Operating Manual ...
Page 208: ...Maintenance and Servicing 11 03 SINAMICS G150 11 12 Operating Manual ...
Page 234: ......
Page 238: ...Parameterlist 11 03 SINAMICS G150 Parameterlist 4 Operating Manual ...
Page 239: ......