Electrical installation
4.9 Signal connections
Converter cabinet units
106
Operating Instructions, 07/2016, A5E03347396A
T0, T1, T2: Measuring socket contacts
Table 4- 17 Measuring socket contacts T0, T1, T2
Socket
Function
Technical data
M
Ground
Voltage: 0… 5 V
Resolution: 8 bits
Load current: max. 3 mA
Continuous short-circuit proof
The reference potential is terminal M
T0
Measuring socket contact 0
T1
Measuring socket contact 1
T2
Measuring socket contact 2
PCB plug connector from Phoenix Contact, type: ZEC 1.0/ 4-ST-3.5 C1 R1.4, order number: 1893708
Note
Cable cross section
The measuring socket contacts are only suitable for cable cross-sections of 0.2 mm
2
to
1 mm
2
.
Note
Using the measuring socket contacts
The measuring socket contacts support commissioning and diagnostic functions. It must not
be connected for normal operation.
DIAG button
The DIAG pushbutton is reserved for service functions.