Commissioning
5.3 Procedure for commissioning with STARTER
Converter cabinet units
212
Operating Instructions, 07/2016, A5E03347396A
⇒
Select the corresponding settings for the closed-loop control structure:
●
Function modules:
–
Technology controller
–
Extended messages/monitoring
●
Control:
–
n/M c V/f control, I/f control
–
V/f control
●
Control mode:
Depending on the selected control, you can select from one of the following open-
loop/closed-loop control modes:
–
0: V/f control with linear characteristic
–
1: V/f control with linear characteristic and FCC
–
2: V/f control with parabolic characteristic
–
3: V/f control with parameterizable characteristic
–
4: V/f control with linear characteristic and ECO
–
5: V/f control for drive requiring a precise frequency (e.g. textiles)
–
6: V/f control for drive requiring a precise frequency and FCC
–
7: V/f control with parabolic characteristic and ECO
–
15: Operation with braking resistor
–
18: I/f control with fixed current
–
19: V/f control with independent voltage setpoint
–
20: Speed control (without encoder)
–
21: Speed control (with encoder)
–
22: Torque control (without encoder)
–
23: Torque control (with encoder)
⇒
Click Continue >