Operation
6.6 Control via the operator panel
Converter cabinet units
300
Operating Instructions, 07/2016, A5E03347396A
Normalization for VECTOR object
Table 6- 6
Normalization for VECTOR object
Size
Scaling parameter
Default for quick commissioning
Reference speed
100% = p2000
p2000 = Maximum speed (p1082)
Reference voltage
100% = p2001
p2001 = 1000 V
Reference current
100% = p2002
p2002 = Current limit (p0640)
Reference torque
100% = p2003
p2003 = 2 x rated motor torque
Reference power
100% = r2004
r2004 = (p2003 x p2000 x π) / 30
Reference frequency
100% = p2000/60
Reference modulation
depth
100 % = Maximum output voltage without overload
Reference flux
100 % = Rated motor flux
Reference temperature
100% = p2006
p2006 = 100°C
Object B_INF
Table 6- 7
List of signals for the operation screen - object B_INF
Signal
Parameter
Short name Unit
Scaling (100 %=...) See
table below
Factory setting (entry no.)
DC link voltage smoothed
(1)
r0026
U_DC
V
p2001
Temperature of power unit
(2)
r0037
T_LT
°C
p2006
Normalization for object B_INF
Table 6- 8
Normalization for object B_INF
Variable
Normalization parameters
Default for quick commissioning
Reference voltage
100% = p2001
p2001 = r0206/r0207
Reference temperature
100% = p2006
p2006 = 100°C