6.13 Communication services and used port numbers
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
411
•
r8854
COMM BOARD state
•
p8920[0...239] PN Name of Station
•
p8921[0...3] PN IP address
•
p8922[0...3] PN default gateway
•
p8923[0...3
PN Subnet Mask
•
p8924
PN DHCP mode
•
p8925
PN interfaces configuration
•
p8940[0...239] CBE2x Name of Station
•
p8941[0...3] CBE2x IP address
•
p8942[0...3] CBE2x Default Gateway
•
p8943[0...3] CBE2x Subnet Mask
•
p8944
CBE2x DHCP mode
•
p8945
CBE2x interfaces configuration
Faults and alarms
•
F01910
Fieldbus: Setpoint timeout
•
A01925
Modbus TCP connection interrupted
•
F08501
PN/COMM BOARD: Setpoint timeout
•
A08526
PN/COMM BOARD: No cyclic connection
•
A08555
Modbus TCP commissioning fault
6.13
Communication services and used port numbers
The drive device supports the protocols listed in the following table. The address
parameters, the relevant communication layer as well as the communication role and the
communication direction are specified for each protocol.
This information allows you to match the security measures for the protection of the
automation system to the used protocols (e.g. firewall). As the security measures are limited
to Ethernet and PROFINET networks, no PROFIBUS protocols are listed in the table.
The following table shows the various layers and protocols that are used.