Operation
6.14 Parallel operation of communication interfaces
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
415
Note
Parallel operation of PROFIBUS and PROFINET
The data of isochronous applications can only be processed via one of the two interfaces IF1
or IF2 (p8815). 2 parameterization options are available if additionally the PROFINET
module CBE20 is inserted in the CU320-2 DP:
- p8839[0] = 1 and p8839[1] = 2: PROFIBUS isochronous, PROFINET cyclic
- p8839[0] = 2 and p8839[1] = 1: PROFINET isochronous, PROFIBUS cyclic
Parameters for IF2
The following parameters are available in order to optimize the IF2 for a PROFIBUS or
PROFINET interface:
●
Receive and send process data:
r8850, p8851, r8853, r8860, p8861, r8863
1)
●
Diagnostic parameters:
r8874, r8875, r8876
1)
●
Binector-connector converters:
p8880, p8881, p8882, p8883, p8884, r8889
1)
●
Connector-binector converters:
r8894, r8895, p8898, p8899
1)
1)
Significance of 88xx identical to 20xx
Note
Using the HW Config configuration tool, a PROFIBUS slave / PROFINET device with two
interfaces cannot be shown. In parallel operation, this is the reason that SINAMICS drive
appears twice in the project or in 2 projects, although physically it is just one device.