Output terminals
8.2 Analog outputs
Converter cabinet units
470
Operating Instructions, 07/2016, A5E03347396A
8.2
Analog outputs
Description
When using option G60, the customer terminal strip has two analog outputs two output
setpoints via current or voltage signals.
Delivery condition:
●
AO0: Actual speed value 0 to 20 mA
●
AO1: Actual motor current, 0 to 20 mA
Signal flow diagram
Figure 8-1
Signal flow diagram: analog output 0
Function diagram
FP 1840,
FP 9572
TM31 - analog outputs (AO 0 to AO 1)
Parameter
•
p4071
TM31 analog outputs, signal source
•
p4073
TM31 analog outputs, smoothing time constant
•
r4074
Analog outputs, actual output voltage/current
•
p4076
TM31 analog outputs, type
•
p4077
TM31 analog outputs, characteristic, value x1
•
p4078
TM31 analog outputs, characteristic, value y1
•
p4079
TM31 analog outputs, characteristic, value x2
•
p4080
TM31 analog outputs, characteristic, value y2