Functions, monitoring, and protective functions
9.2 Drive functions
Converter cabinet units
500
Operating Instructions, 07/2016, A5E03347396A
WARNING
Danger to life as a result of unexpected motor movement when activating flying restart
When the flying restart (p1200) function is active, the drive may still be accelerated by
the search current despite the fact that it is at standstill and the setpoint is 0!
For this reason, death, serious injury, or considerable material damage can occur if
personnel enter the working area of a motor in this state.
•
Observe the general safety instructions.
•
Ensure that the EMERGENCY STOP functions are always fully functional.
9.2.6.3
Parameters
•
p0352
Cable resistance
•
p1200
Flying restart operating mode
•
0: Flying restart inactive
•
1: Flying restart always active (start in setpoint direction)
•
2: Flying restart active after On, error, OFF2 (start in setpoint direction)
•
3: Flying restart active after error, OFF2 (start in setpoint direction)
•
4: Flying restart always active (start only in setpoint direction)
•
5: Flying restart active after On, error, OFF2 (start only in setpoint
direction)
•
6: Flying restart active after error, OFF2 (start only in setpoint direction)
•
p1202
Flying restart search current
•
p1203
Flying restart search speed factor
•
r1204
Flying restart, V/f control status
•
r1205
Flying restart, vector control status
Note
Set search direction for the flying restart
For p1200 = 1, 2, 3, the following applies: Search in both directions, start only in the setpoint
direction.
For p1200 = 4, 5, 6, the following applies: Search only in the setpoint direction.
Summary of Contents for SINAMICS G150
Page 1: ......
Page 2: ......
Page 8: ...Foreword Converter cabinet units 8 Operating Instructions 07 2016 A5E03347396A ...
Page 18: ...Table of contents Converter cabinet units 18 Operating Instructions 07 2016 A5E03347396A ...
Page 679: ......
Page 680: ......