Functions, monitoring, and protective functions
9.3 Extended functions
Converter cabinet units
554
Operating Instructions, 07/2016, A5E03347396A
Figure 9-15 Typical circuit diagram for bypass with synchronizer with degree of overlapping
Activation
The synchronized bypass with overlap (p1260 = 1) function can only be activated using a
control signal. It cannot be activated using a speed threshold.
Parameterization
Once the bypass with synchronizer with degree of overlapping (p1260 = 1) function has
been activated, the following parameters must be set:
Table 9- 7
Parameter settings for bypass function with synchronizer with degree of overlapping
Parameters
Description
r1261.0
Signal "Command switch motor - power unit"
r1261.1
Signal "Command switch motor - line supply"
p1266 =
Control signal setting
p1269[0] =
Signal source for contactor K1 feedback
p1269[1] =
Signal source for contactor K2 feedback
p3800 = 1
Synchronization is activated
p3802 = r1261.2 Synchronizer activation is triggered by the bypass function.