Functions, monitoring, and protective functions
9.4 Monitoring and protective functions
Converter cabinet units
584
Operating Instructions, 07/2016, A5E03347396A
Commissioning the motor model
The thermal I2t motor model is activated via p0612.0 = 1, the expansions of the motor model
can additionally be activated via p0612.8 = 1.
Note
When commissioning the motor, thermal motor model 1 (p0612.0 = 1) including expansion
(p0612.8 = 1) is automatically activated.
Preconditions for automatic activation:
•
Use of a permanent magnet synchronous motor
•
There is no motor sensor
•
No (other) thermal motor model is activated
Important settings
The most important parameters for thermal motor model 1 and/or for the expansion of this
model are subsequently explained.
When the expansion is subsequently activated, the corresponding parameters of the
expansion are preassigned with the parameter values before activating the expansion.
Parameters for the following
settings
Explanation
p0612.8 = 0
p0612.8 = 1
p0605
p5390
Alarm threshold
If the model motor temperature (r0632) exceeds the alarm threshold, alarm A07012
"Drive: Motor temperature model 1/3 overtemperature" is output.
p0615
p5391
Fault threshold
If the model motor temperature (r0632) exceeds the fault threshold, fault F07011
"Drive: Motor overtemperature" is output.
p0605
p0627 + 40 °C Rated temperature (winding)
Defines the rated overtemperature of the stator winding referred to the ambient tem-
perature.
1.333 (fixed
value)
p5350
Boost factor
Defines the boost factor for the copper losses at standstill.
p0612 = 0x1
p0612 = 0x101 Activation
Activates the motor module and/or additionally the expansion.
r0632
r0632
Actual temperature
Indicates the stator winding temperature of the motor temperature model.
r0034
r0034
Motor utilization
Indicates the actual motor utilization level.
Summary of Contents for SINAMICS G150
Page 1: ......
Page 2: ......
Page 8: ...Foreword Converter cabinet units 8 Operating Instructions 07 2016 A5E03347396A ...
Page 18: ...Table of contents Converter cabinet units 18 Operating Instructions 07 2016 A5E03347396A ...
Page 679: ......