Maintenance and servicing
11.8 Load the new operator panel firmware from the PC
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
643
11.8
Load the new operator panel firmware from the PC
Description
Firmware might need to be loaded to the AOP if the AOP functionality needs to be upgraded.
If, once the drive has being switched on, the memory card is found to contain a newer
version of the firmware, a message will appear on the AOP30 prompting you to load the new
firmware. You should click "YES" in response to this prompt.
The firmware will then be loaded automatically on the operator panel and the following dialog
screen will appear.
Figure 11-15 Dialog screen: loading firmware
If the firmware cannot be loaded successfully, it can be loaded using the following manual
method.
The load program LOAD_AOP30 and the firmware file can be found on the customer DVD.
Loading the firmware
1.
Establish the RS232 connection from the PC to the AOP30.
2.
Provide the supply voltage (24 V DC).
3.
Start the LOAD_AOP30 program on the PC.
4.
Choose the PC interface (COM1, COM2).
5.
Choose and open the firmware (AOP30.H86).
6.
Follow the instructions in the status window of the program and connect the power supply
for the AOP30 while pressing the red key (O).
7.
The load procedure is started automatically.
8.
Switch the power on (switch the power supply off and then back on).
Summary of Contents for SINAMICS G150