Technical specifications
12.2 General data
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
647
Mechanical strength
Storage
Transport
Operation
Vibrational load
2)
- Displacement
- Acceleration
corresponds to class
1.5 mm at
5
to 9 Hz
5 m/s² at > 9 to 200 Hz
1M2 to EN 60721-3-1
3.1 mm
at
5
... 9 Hz
10 m/s² at > 9 ... 200 Hz
2M2 to EN 60721-3-2
0.075 mm at 10 ... 58 Hz
10 m/s² at >58 ... 200 Hz
-
Shock load
2)
- Acceleration
corresponds to class
40 m/s² at 22 ms
1M2 to EN 60721-3-1
100 m/s² at 11 ms
2M2 to EN 60721-3-2
100 m/s² at 11 ms
3M4 to EN 60721-3-3
Deviations from the defined classes are shown in
italics
.
1)
Applies to cable lengths of up to 100 m.
2)
The EN standards specified are the European editions of the international IEC standards with the same designations.
12.2.1
Derating data
12.2.1.1
Current derating as a function of the ambient temperature
Permissible output current as a function of the ambient temperature
The cabinet devices and the associated system components are rated for an ambient
temperature of 40 °C and installation altitudes up to 2000 m above sea level. The output
current must be reduced if the cabinet devices are operated at ambient temperatures above
40 °C. Ambient temperatures above 50 °C are not permissible. The following tables specify
the permissible output current as a function of the ambient temperature for the different
degrees of protection .
Table 12- 2 Current derating factors as a function of the ambient temperature (inlet air temperature at the air inlet of the
cabinet unit) and installation altitude for cabinet units with degree of protection IP20/IP21/IP23/IP43
Installation altitude
above sea level in m
Current derating factor
at an ambient temperature (air intake temperature) of
20 °C
25 °C
30 °C
35 °C
40 °C
45 °C
50 °C
0 ... 2000
100 %
100 %
100 %
100 %
100 %
93.3 %
86.7 %
Table 12- 3 Current derating factors as a function of the ambient temperature (inlet air temperature at the air inlet of the
cabinet unit) and installation altitude for cabinet units with degree of protection IP54
Installation altitude
above sea level in m
Current derating factor
at an ambient temperature (air intake temperature) of
20 °C
25 °C
30 °C
35 °C
40 °C
45 °C
50 °C
0 ... 2000
100 %
100 %
100 %
100 %
93.3 %
86.7 %
80.0 %
Summary of Contents for SINAMICS G150
Page 1: ......
Page 2: ......
Page 8: ...Foreword Converter cabinet units 8 Operating Instructions 07 2016 A5E03347396A ...
Page 18: ...Table of contents Converter cabinet units 18 Operating Instructions 07 2016 A5E03347396A ...
Page 679: ......
Page 680: ......