Appendix
A.2 Parameter macros
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
669
Parameter macro p1000 = 1: PROFIdrive (100001)
This macro is used to set the default setpoint source via PROFIdrive.
Table A- 6
Parameter macro p1000 = 1: PROFIdrive
Sink
Source
Parameters
Description
DO
Parameters
Description
DO
p1070
Main setpoint
Vector
r2050[1]
PROFIdrive PZD2
Vector
p1071
Main setpoint scaling
Vector
1
100 %
Vector
p1075
Supplementary setpoint
Vector
0
Vector
p1076
Supplementary setpoint scaling
Vector
1
100 %
Vector
Parameter macro p1000 = 2: Terminal TM31 (100002)
This macro is used to set analog input 0 on customer terminal block TM31 as the setpoint
source.
Table A- 7
Parameter macro p1000 = 2: TM31 terminals
Sink
Source
Parameter
Description
DO
Parameter
Description
DO
p1070
Main setpoint
Vector
r4055
AI0 TM31
TM31
p1071
Main setpoint scaling
Vector
1
100 %
Vector
p1075
Supplementary setpoint
Vector
0
Vector
p1076
Supplementary setpoint scaling
Vector
1
100 %
Vector
Parameter macro p1000 = 3: Motorized potentiometer (100003)
This macro is used to set the motorized potentiometer as the setpoint source.
Table A- 8
Parameter macro p1000 = 3: Motorized potentiometer
Sink
Source
Parameters
Description
DO
Parameters
Description
DO
p1070
Main setpoint
Vector
r1050
Motorized potentiometer
Vector
p1071
Main setpoint scaling
Vector
1
100 %
Vector
p1075
Supplementary setpoint
Vector
0
Vector
p1076
Supplementary setpoint scaling
Vector
1
100 %
Vector