LEDs of the DM10 diagnostics module
The LEDS installed on the diagnosis module indicate the logic state of the signals present
between the communication partners of the DM10 diagnosis module.
Table 8-10
LEDs of the DM10 diagnostics module
LED Communication partner
Meaning: signal 1 / signal 0
H30
-X232/-X32
Control signals from PSA present / not present
H31
-X232/-X32
Control signals from PSA present / not present
H32
-X232/-X32
Control signals from PSA present / not present
H33
-X232/-X32
Control signals from PSA present / not present
H34
-X33/-X5
Binary plant signals for diagnosis on PADU8 present / not present
H35
-X33/-X5
Binary plant signals for diagnosis on PADU8 present / not present
H36
-X33/-X5
Binary plant signals for diagnosis on PADU8 present / not present
H37
-X33/-X5
Binary plant signals for diagnosis on PADU8 present / not present
H20
-X34/-X36
Internal power supply 1P24 OK / not OK
H21
-X34/-X36
Internal power supply 1N24 OK / not OK
H22
-X35/-X36
External power supply 2P24_1 and 2P24_2 OK / 2P24_1 or 2P24_2 not OK
H23
-
Internal and external power supplies OK / not OK
8.6.3.3
Diagnostics via parameters
Diagnostic parameters for the device status
r0002
Drive status
Display of drive status
r0046
Missing enable signals
Display of the missing enable signals that are preventing the drive control from being commissioned
Bit
Signal name
0-signal
1-signal
00
OFF1 enable missing
No
Yes
01
OFF2 enable missing
No
Yes
02
OFF3 enable missing
No
Yes
03
Enable run missing
No
Yes
05
External power-on inhibit active
No
Yes
06
Commissioning not yet complete
No
Yes
09
Infeed enable missing
No
Yes
10
Ramp-function generator enable missing
No
Yes
11t
No start ramp-function generator
No
Yes
12t
No setpoint enable
No
Yes
16
OFF1 internal enable missing
No
Yes
17
OFF2 internal enable missing
No
Yes
Operation
8.6 Fault and system messages
SINAMICS GM150 6SL3835-2LN44-2AA0
Operating Instructions Rev.201910281250 MUSTER