Checklists and forms
C
C.1
Mechanical installation: Checklist
Logbook
Use the following checklist to guide you through the mechanical installation procedure for the
cabinet unit. Read the safety information at the start of these operating instructions before you
start working on the device.
Note
If the option in question is part of the delivery, check this accordingly in the right-hand column.
Check the boxes once you have finished the installation procedure to confirm that the activities
are complete.
Activity
Available / Completed
The environmental conditions must be permissible. For more infor‐
mation, see the "Technical specifications" section.
If the drive and re-cooling unit are installed separately, the bottom
level (switch-off level) of the expansion tank must be located above
the highest water level in the drive.
Connect the raw water circuit and the de-ionized water circuit. Re‐
move any contamination from the piping that may have occurred dur‐
ing shipment or storage.
Fill and vent the de-ionized water circuit according to the specifica‐
tions. Ensure that no air is trapped in the piping system.
Install the separately supplied components. Make the required me‐
chanical and electrical connections as well as the connection to the
de-ionized water circuit.
The clearance around an open door (escape route) specified in the
applicable accident prevention guidelines must be observed.
For option M13/M78:
Select the required metric gland or PG gland appropriate for the cable
cross-section. Proivde the appropriate holes in the cover plates.
When the cable is fed in from above, ensure that enough room is
available if the cable has to be bent because of the cable feeder and
cross-sections. To prevent lateral forces on the entries, insert the
cable vertically.
SINAMICS GM150 6SL3835-2LN44-2AA0
Operating Instructions Rev.201910281250 MUSTER
223
Summary of Contents for Sinamics GM150 6SL3835-2LN44-2AA0
Page 2: ...28 10 2019 12 50 V32 00 ...
Page 232: ...Index SINAMICS GM150 6SL3835 2LN44 2AA0 232 Operating Instructions Rev 201910281250 MUSTER ...
Page 233: ......
Page 236: ......
Page 238: ......